Print Report | Back to Sample Detail

Sample Record for 2017-09-26-1

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 88888 DEA: SMTL-STOCK EFIS: SMTL-STOCK QA Service Level:
DIST-CO-RTE-PM: 59---
Work Description: Special project for SMTL stock material. Object Code: 1025. J2 DEA: 912680.
Location Description:
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2017-09-26-1
TL Number from the TL Form: Unknown
Sample Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Sample Organization Contact: (916) 227-7071
Type of Sample: Annual Source Testing
Type of Material: Cementitious
Sample Taken Date: 09/26/2017
Date that the sample was received by the laboratory/organization performing the testing: 09/26/2017
The quantity of what the sample constitutes: 1 Bucket
A brief description of the sample: Type IP
From where was the sample collected: Source
Laboratory sample identification: CM175720
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Nevada Cement

Material Information

Brand: Nevada Cement
Mill: Fernley Nevada
Type of Cementitious Material: Blended Cement

Test Results

Test 1 of 8

DIME Test ID: 2017-09-26-1-2
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 08/08/2018
Date Tested: 10/12/2017
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 3 Day Break
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311? no
Compressive strength of 1st specimen (psi) 2674 psi
Compressive strength of 2nd specimen (psi) 2676 psi
Compressive strength of 3rd specimen (psi) 2886 psi
Average Compressive strength (to nearest 10 psi) 2750 psi

Test 2 of 8

DIME Test ID: 2017-09-26-1-3
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 08/08/2018
Date Tested: 10/16/2017
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 7 Day Break
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311? no
Compressive strength of 1st specimen (psi) 3564 psi
Compressive strength of 2nd specimen (psi) 3506 psi
Compressive strength of 3rd specimen (psi) 3444 psi
Average Compressive strength (to nearest 10 psi) 3500 psi

Test 3 of 8

DIME Test ID: 2017-09-26-1-4
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 08/08/2018
Date Tested: 11/06/2017
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 28 Day Break
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311? no
Compressive strength of 1st specimen (psi) 4881 psi
Compressive strength of 2nd specimen (psi) 4418 psi
Compressive strength of 3rd specimen (psi) 4616 psi
Average Compressive strength (to nearest 10 psi) 4640 psi

Test 4 of 8

DIME Test ID: 2017-09-26-1-5
Test Method: ASTM C188-15: Standard Test Method for Density of Hydraulic Cement
Verified Date: 02/13/2019
Date Tested: 02/14/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Density of hydraulic cement 2.959 g/cm^3

Test 5 of 8

DIME Test ID: 2017-09-26-1-6
Test Method: ASTM C185-15a: Standard Test Method for Air Content of Hydraulic Cement Mortar
Verified Date: 08/08/2018
Date Tested: 10/06/2017
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Specific gravity 3.15
Water Content 244 mL
The amount of flow (In percent) 92 %
The amount of water used (In percent) 69.7 %
Net Weight of Sample 820.2 grams
Air Content 9.15 %

Test 6 of 8

DIME Test ID: 2017-09-26-1-7
Test Method: ASTM C191-13: Standard Test Methods for Time of Setting of Hydraulic Cement by Vicat Needle
Verified Date: 08/08/2018
Date Tested: 11/02/2017
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Type of Water Used Type III grade reagent water
Initial time of setting 186 min
Final time of setting 187 min

Test 7 of 8

DIME Test ID: 2017-09-26-1-8
Test Method: ASTM C204-11: Standard Test Methods for Fineness of Hydraulic Cement by Air-Permeability Apparatus
Verified Date: 08/08/2018
Date Tested: 02/16/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Method Used Test Method A
Test Time 99 seconds
Fineness 4524 cm^2/g

Test 8 of 8

DIME Test ID: 2017-09-26-1-9
Test Method: ASTM C430-8: Standard Test Method for Fineness of Hydraulic Cement by the 45-μm (No. 325) Sieve
Verified Date: 08/08/2018
Date Tested: 12/07/2017
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Corrected residue, % (Rc) 5.3 %
Fineness of the cement as the corrected percentage passing the 45 micrometers sieve (No. 325) 94.7 %