Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 209146 DEA: 06471504 EFIS: 0600000464 COOP: 061549
QA Service Level: 1
DIST-CO-RTE-PM: 06-TUL-99-39.6/41.3
Work Description: RECONSTRUCT INTERCHANGE WITH NEW PUMPING PLANT.
Location Description: TULARE COUNTY AT GOSHEN FROM 0.9 MILE NORTH OF ROUTE 99/198 WEST SEPARATION TO 0.2 MILE NORTH OF NORTH GOSHEN OVERHEAD
Contractor Name: GRANITE CONSTRUCTION COMPANY
Contractor Address: 2716 Granite Court, Fresno, CA 93706
Resident Engineer: Brent Haroldsen Structure Rep.: Peter Moua
DIME Sample ID: 2017-08-01-5
TL Number from the TL Form: Unknown
Sample Submitted By Organization: CT HQ - QASI Bay Area Field Office
Sample Organization Contact: (916) 284-6784
Type of Sample: Verification
Type of Material: SMTL TM7 - Epoxy Coated Rebar
Sample Taken Date: 08/01/2017
Date that the sample was received by the laboratory/organization performing the testing: 08/02/2017
The quantity of what the sample constitutes: 1 truck load
A brief description of the sample: 8 A775 epoxy coated rebar
From where was the sample collected: Fabricator
Laboratory sample identification: Unknown
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Western Coating
Rebar Heat Number(s): PL17104813
Rebar Epoxy Batch Number(s): TD95852NA
Rebar Coating Specification: ASTM A775
Rebar Size (#): 8
Rebar Coating Color: Green
Rebar Manufacturer: Nucor
Rebar Coater: Western Coating
Rebar Powder Manufacturer: Axalta
Release Number: 36401
Quality Assurance Code: Unknown
DIME Test ID: 2017-08-01-5-1
Test Method: ASTM A775-07b-re14: Standard Specification for Epoxy-Coated Steel Reinforcing Bars (Epoxy Coating)
Verified Date: 08/07/2017
Date Tested: 08/04/2017
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
First Bar Mean
|
10.89 mils
|
Second Bar Mean
|
10.51 mils
|
Lower spec. limit LSL
|
7 mils
|
Upper spec. limit USL
|
16 mils
|
Bar # for First Bar
|
no data
|
Bar # for Second Bar
|
no data
|
Total mean value
|
10.7 mils
|
Total number of values less than LSL
|
no data
|
Total number of values greater than USL
|
no data
|
DIME Test ID: 2017-08-01-5-2
Test Method: ASTM A775-07b-re14: Standard Specification for Epoxy-Coated Steel Reinforcing Bars (Holiday)
Verified Date: 08/07/2017
Date Tested: 08/04/2017
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Total Number of Holiday
|
1
|
Total Length
|
5 ft
|
Holidays Per Linear Foot of Bar
|
0.2 holiday pe
|
Holiday Test Pass/Fail
|
Pass
|
Bend Test Pass/Fail
|
Pass
|