Project ID: 88888 DEA: SMTL-STOCK EFIS: SMTL-STOCK
QA Service Level:
DIST-CO-RTE-PM: 59---
Work Description: Special project for SMTL stock material. Object Code: 1025. J2 DEA: 912680.
Location Description:
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown Structure Rep.: Unknown
DIME Sample ID: 2017-05-23-1
TL Number from the TL Form: Unknown
Sample Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Sample Organization Contact: (916) 227-7071
Type of Sample: Control Sample
Type of Material: Cementitious
Sample Taken Date: 05/23/2017
Date that the sample was received by the laboratory/organization performing the testing: 05/23/2017
The quantity of what the sample constitutes: 6 cubes
A brief description of the sample: Control for Fly Ash
From where was the sample collected: Other
Laboratory sample identification: CM179008
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Nevada Cement
DIME Test ID: 2017-05-23-1-1
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 03/22/2019
Date Tested: 05/30/2017
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 7 Day Break Control
Test Result Compliance: complies
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
no
|
Compressive strength of 1st specimen (psi)
|
3755 psi
|
Compressive strength of 2nd specimen (psi)
|
3922 psi
|
Compressive strength of 3rd specimen (psi)
|
3895 psi
|
Average Compressive strength (to nearest 10 psi)
|
3860 psi
|
DIME Test ID: 2017-05-23-1-2
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 03/22/2019
Date Tested: 06/20/2017
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 28 Day Break Control
Test Result Compliance: complies
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
no
|
Compressive strength of 1st specimen (psi)
|
4629 psi
|
Compressive strength of 2nd specimen (psi)
|
4585 psi
|
Compressive strength of 3rd specimen (psi)
|
4670 psi
|
Average Compressive strength (to nearest 10 psi)
|
4630 psi
|