Print Report | Back to Sample Detail

Sample Record for 2024-11-07-42

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 44444 DEA: ASCP EFIS: ASCP QA Service Level:
DIST-CO-RTE-PM: 59---
Work Description: Special project for submitting Sample information for Asphalt Supplier Certification Program.
Location Description:
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2024-11-07-42
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Sample Organization Contact: (916) 227-7302
Type of Sample: Verification
Type of Material: Asphalt Binder
Sample Taken Date: 11/07/2024
Date that the sample was received by the laboratory/organization performing the testing: 11/15/2024
The quantity of what the sample constitutes: 1 of 1
A brief description of the sample: Tank 501-Pg 70-10
From where was the sample collected: Manufacturer
Laboratory sample identification: 24-244
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Glendale, AZ

Material Information

Performance Grade: PG 70-10
Modified: No
Lot number:
Sublot number:
Tank number: Tank 501
Time of sample:
HMA Supplier:
Certified Asphalt Supplier: Holly Frontier Asphalt Company - Glendale AZ
Multigrade: No
Multigrade Type:
Asphalt Binder Mix Number:

Test Results

Test 1 of 7

DIME Test ID: 2024-11-07-42-1
Test Method: AASHTO T315-22: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 01/28/2025
Date Tested: 12/21/2024
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Original
Test Result Compliance: complies
Additional Comments When Verified:
Phase Original binder
Test Gap 1 mm
Test Frequency 10.0 rad/s
Strain Amplitude 12.06 %
Stress Amplitude 0.141 kPa
Phase Angle (δ) (for the 10 cycles) 88.2 degree
Complex Modulus (G*) (for the 10 measurements) 1.168 kPa
Test Temperature (Specimen 1) 70.0 C
Dynamic Shear, G*/sin(δ) 1.17 kPa

Test 2 of 7

DIME Test ID: 2024-11-07-42-2
Test Method: AASHTO T315-22: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 01/28/2025
Date Tested: 12/22/2024
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: RTFO
Test Result Compliance: complies
Additional Comments When Verified:
Phase RTFO residue
Test Gap 1 mm
Test Frequency 10.0 rad/s
Strain Amplitude 10.05 %
Stress Amplitude 0.296 kPa
Phase Angle (δ) (for the 10 cycles) 85.6 degree
Complex Modulus (G*) (for the 10 measurements) 2.942 kPa
Test Temperature (Specimen 1) 70.0 C
Dynamic Shear, G*/sin(δ) 2.95 kPa

Test 3 of 7

DIME Test ID: 2024-11-07-42-3
Test Method: AASHTO T315-22: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 01/28/2025
Date Tested: 12/23/2024
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: PAV
Test Result Compliance: complies
Additional Comments When Verified:
Phase PAV residue
Test Plate Diameter 8 mm
Test Gap 2 mm
Test Frequency 10.0 rad/s
Strain Amplitude 1.01 %
Stress Amplitude 69.375 kPa
Phase Angle (δ) (for the 10 cycles) 44.2 degree
Complex Modulus (G*) (for the 10 measurements) 6,902.764 kPa
Test Temperature (Specimen 1) 34.0 C
(G*) x sin(δ)= 4812 kPa

Test 4 of 7

DIME Test ID: 2024-11-07-42-4
Test Method: AASHTO T51-22: Standard Method of Test for Ductility of Asphalt Materials (Asphalt Binder)
Verified Date: 01/28/2025
Date Tested: 12/23/2024
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: DUCT
Test Result Compliance: complies
Additional Comments When Verified:
Is a normal test obtainable? Yes
Number of replicates tested One
Ductility of test #1 (D1) 86 cm
Ductility of sample 86 cm

Test 5 of 7

DIME Test ID: 2024-11-07-42-5
Test Method: AASHTO T313-22: Standard Method of Test for Determining the Flexural Creep Stiffness of Asphalt Binder Using the Bending Beam Rheometer (BBR)
Verified Date: 01/28/2025
Date Tested: 12/23/2024
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: BBR
Test Result Compliance: complies
Additional Comments When Verified:
Minimum test bath temperature at 240 s no data
Maximum test bath temperature at 240 s no data
Time of test load application no data HH:MM:SS
File name of test data no data
Time beam in bath no data
Time test started no data HH:MM:SS
Flags issued by software during test no data
Correlation coefficient (R²) no data0
Regression coefficient a no data
Regression coefficient b no data
Regression coefficient c no data
Load at time 0.0 0.0 mN
Deflection at time 0.0 s 0.000 µm
Load at time 0.5 s 0.0 mN
Deflection at time 0.5 s 0.000 µm
Load at 60.0 s 0.0 mN
Beam deflection 60.0 s 0.000 µm
Measured Stiffness Modulus 60.0 s 81.000 mPa
Estimated Stiffness Modulus 60.0 s no data
Difference between stiffness moduli 60.0 s no data
Estimated m-value 60.0 s 0.341

Test 6 of 7

DIME Test ID: 2024-11-07-42-8
Test Method: AASHTO T44-18: Standard Method of Test for Solubility of Bituminous Materials
Verified Date: 01/28/2025
Date Tested: 12/23/2024
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: SOLUBILITY
Test Result Compliance: complies
Additional Comments When Verified:
Was test performed on residue from distillation or evaporation? Evaporation
Soluble, percent 99.9 %
Insoluble, percent 0.0 %

Test 7 of 7

DIME Test ID: 2024-11-07-42-9
Test Method: AASHTO T316-17: Standard Method of Test for Viscosity Determination of Asphalt Binder Using Rotational Viscometer
Verified Date: 01/28/2025
Date Tested: 12/23/2024
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: VISC
Test Result Compliance: complies
Additional Comments When Verified:
Is viscosity reading in cP/Pa-s? Pa-s
Time of test 9:00 HH:MM
Test Temperature 135.0 C
Speed 20 rpm
Spindle size 0.66 in
Torque 21.8 %
Viscosity reading #1 (A) 0.545 Pa-s
Viscosity reading #2 (B) 0.545 Pa-s
Viscosity reading #3 (C) 0.545 Pa-s
Average viscosity 0.545 Pa-s