Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 211661 DEA: 120P1904 EFIS: 1215000050 MINOR: 12A1621
QA Service Level: 1
DIST-CO-RTE-PM: 12--5-13.57
Work Description: Involves removing (4) Electroliers and installing (5) Electroliers.
Location Description: The Department of Transportation (Department) will receive sealed bids for CONSTRUCTION ON STATE HIGHWAY IN City of Mission Viejo. District-County-Route-Post Mile: 12-Ora-Route 5-PM 13.57. (Crown Valley Parkway)
Contractor Name: BECDEL
Contractor Address: 31500 Grape Street, Ste. 444, Lake Elsinore, CA 92532
Resident Engineer: Danh Thai Structure Rep.: Unknown
DIME Sample ID: 2017-01-26-9
TL Number from the TL Form: C953666
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (530) 329-6527
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Welded Hoops
Sample Taken Date: 01/26/2017
Date that the sample was received by the laboratory/organization performing the testing: 01/30/2017
The quantity of what the sample constitutes: 4
A brief description of the sample: Flash Welded Rebar Hoops
From where was the sample collected: Fabricator
Laboratory sample identification: Unknown
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: TNT Rebar
Production or Authorization Testing: Authorization Testing
Service or Ultimate: Service
Rebar Heat Number(s): 4049973
Hoop Manufacturer Lot Number(s): 1
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Size: 4
Diameter of Hoop: 2'-2"
Epoxy Coated: No
Epoxy Coating Color: NA
Rebar Manufacturer: CMC
Welding Company: TNT Rebar
Coating Standards: Uncoated
Weld Type: Flash Welded
DIME Test ID: 2017-01-26-9-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/31/2017
Date Tested: 01/31/2017
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Bar Broke, Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Samples
|
1
|
Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | 1 | 1 | #4/13mm | 0.2 | 19020 | 95100 | Bar Broke, Ok Necking | Brian |
| |
UTM
|
400KIP
|
Temperature
|
72 F
|
DIME Test ID: 2017-01-26-9-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/31/2017
Date Tested: 01/31/2017
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Bar Broke; OK Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Samples
|
1
|
Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | 2 | 1 | #4/13mm | 0.2 | 19040 | 95200 | Bar Broke | Brian |
| |
UTM
|
400KIP
|
Temperature
|
72 F
|
DIME Test ID: 2017-01-26-9-3
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/31/2017
Date Tested: 01/31/2017
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Bar Broke; OK Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Samples
|
1
|
Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | 3 | 1 | #4/13mm | 0.2 | 18140 | 90700 | Bar Broke | Brian |
| |
UTM
|
400KIP
|
Temperature
|
72 F
|