Project ID: 993141 DEA: 060V1204 EFIS: 0616000207
QA Service Level: 1
DIST-CO-RTE-PM: 06-MAD-99-R6.9/R7.6
Work Description: Cottonwood Creek Bridge Replacement - REPLACE BRIDGES AND CONSTRUCT RETAINING WALLS.
Location Description: MADERA COUNTY NEAR MADERA FROM 0.4 MILE SOUTH OF COTTONWOOD CREEK BRIDGE TO 0.1 MILE NORTH OF AVENUE 12 OVERCROSSING
Contractor Name: Security Paving Company, Inc.
Contractor Address: 3075 Townsgate Road, Westlake Village CA 91361
Resident Engineer: Din Dadawalla Structure Rep.: Ye Yang
DIME Sample ID: 2024-09-04-26
TL Number from the TL Form:
Sample Submitted By Organization: CT D06 - Millbrook Field Laboratory
Sample Organization Contact: (559) 341-3953
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 09/04/2024
Date that the sample was received by the laboratory/organization performing the testing: 09/05/2024
The quantity of what the sample constitutes: 300CY
A brief description of the sample: Structure Concrete- Deck
From where was the sample collected: Job Site
Laboratory sample identification: 189
Structure unique identifier:
Structure name: Mainline Cottonwood Creek
The fabricator/manufacturer/facility name: Builders Concrete
The concrete mix design number: ND20507
The truck number from where the sample was collected: 9227
The batch plant ticket number from where the sample was collected: 1362757
Concrete batch plant: Builders
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: tailgate
Where the material sample would have been placed if not sampled: bridge deck
From Lot No.:
Bag Lot No.:
DIME Test ID: 2024-09-04-26-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 10/03/2024
Date Tested: 10/03/2024
Submitted By Organization: CT D06 - Millbrook Field Laboratory
Organization Address: 1352 W. Olive Ave,
Organization City: Fresno
Organization State: CA
Organization Zipcode: 93728
Organization Email: tomas.silva@dot.ca.gov
Organization Phone: (559) 417-5341
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4740 psi
|
|
Maximum load on cylinder 1
|
57930 lb
|
|
Maximum load on cylinder 2
|
59410 lb
|
|
Maximum load on cylinder 3
|
61380 lb
|
|
Compressive strength of cylinder 1
|
4608.6 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
4726.3 psi
|
|
Compressive strength of cylinder 3
|
4883.1 psi
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Type of fracture pattern of cylinder 3
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
29 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2024-09-04-26-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 10/03/2024
Date Tested: 10/03/2024
Submitted By Organization: CT D06 - Millbrook Field Laboratory
Organization Address: 1352 W. Olive Ave,
Organization City: Fresno
Organization State: CA
Organization Zipcode: 93728
Organization Email: tomas.silva@dot.ca.gov
Organization Phone: (559) 417-5341
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4930 psi
|
|
Maximum load on cylinder 1
|
61980 lb
|
|
Maximum load on cylinder 2
|
62540 lb
|
|
Maximum load on cylinder 3
|
61550 lb
|
|
Compressive strength of cylinder 1
|
4930.8 psi
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Compressive strength of cylinder 2
|
4975.3 psi
|
|
Compressive strength of cylinder 3
|
4896.6 psi
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Type of fracture pattern of cylinder 3
|
3
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
29 days
|
|
Age of specimen in hours
|
no data0 hours
|