REPORT OF LABORATORY TESTING |
||||
|
Resident Engineer: |
Joni Tji |
Date Reported: |
09/16/2024 |
|
|
Address: |
TL Number: |
133688 |
||
|
City: |
||||
|
Project Name: Deck rehab with RSC. New Approach Slabs. New Barriers. |
||||
|
Prime Contractor: GRANITE CONSTRUCTION |
||||
|
Sample Taken Date: |
08/18/2024 |
Mix Design: |
1629682 |
|
|
Contractor: Unknown |
Location : Br 24-0207L/R. Br 24-0068L |
|||
|
Structure unique identifier: |
||||
|
Structure name: |
||||
|
Location of Pour: |
||||
The following testing has been tested in accordance with:
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Cured in accordance with ASTM C511
| Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
|---|---|---|---|---|---|
| 1 | 4.00 | 12.57 | 80639 | 6417.0 | 1 |
| 2 | 4.00 | 12.57 | 84650 | 6736.0 | 1 |
| 3 | 4.00 | 12.57 | 89514 | 7123 | 1 |
DIME Test ID: 2024-08-18-4-1
Number of specimens: 3
Compressive strength (to nearest 10 psi): 6760
Age of specimen: 3 days
Certified By: Spencer Adams
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Cured in accordance with ASTM C511
| Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
|---|---|---|---|---|---|
| 1 | 4.00 | 12.57 | 90524 | 7204.0 | 4 |
| 2 | 4.02 | 12.69 | 94151 | 7418.0 | 2 |
| 3 | 4.02 | 12.69 | 99176 | 7814 | 2 |
DIME Test ID: 2024-08-18-4-2
Number of specimens: 3
Compressive strength (to nearest 10 psi): 7480
Age of specimen: 29 days
Certified By: Spencer Adams
|
*Subject to final inspection by the Resident Engineer. |
|
TL- Report of Laboratory Testing