Gavin Newsom, Governor |
DEPARTMENT OF TRANSPORTATIONDIVISION OF ENGINEERING SERVICES MATERIALS ENGINEERING AND TESTING SERVICES Concrete Materials Testing Branch 5900 Folsom Blvd. Sacramento, CA 95819 916-227-7205 |
Contract # 030H08U4 Cty SAC Rte 50 PM L0.2/R6.1 Vendor # |
REPORT OF LABORATORY TESTING |
||||
Resident Engineer: |
Jim Rogers |
Date Reported: |
09/04/2024 |
|
Address: |
TL Number: |
136082 |
||
City: |
||||
Project Name: Sac 50 Design Build PLEASE NOTE THAT DESIGN BUILDER MUST PERFORM QUALITY VALIDATION TESTING IN ACCORDANCE WITH THE MATERIAL CONTROL SCHEDULE (MCS) FOR ITEMS SUCH AS STRANDS, HS BOLTS, ELASTOMERIC BEARING PADS, JOINT SEALANTS, COUPLERS & WELDED HOOPS, ETC |
||||
Prime Contractor: FLATIRON WEST INC |
||||
Sample Taken Date: |
08/07/2024 |
Mix Design: |
1615776 |
|
Contractor: Unknown |
Location : FROM 0.1 MILE EAST OF I-5 TO 0.8 MILE EAST OF WATT AVE |
|||
Structure unique identifier: |
||||
Structure name: |
||||
Location of Pour: |
The following testing has been tested in accordance with:
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Cured in accordance with ASTM C511
Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 4.01 | 12.63 | 72645 | 5752.0 | 1 |
2 | 4.02 | 12.69 | 69280 | 5458.0 | 1 |
3 | 4.02 | 12.69 | 71166 | 5607 | 1 |
DIME Test ID: 2024-08-07-62-1
Number of specimens: 3
Compressive strength (to nearest 10 psi): 5610
Age of specimen: 28 days
Certified By: Spencer Adams
*Subject to final inspection by the Resident Engineer. |
TL- Report of Laboratory Testing