QA Service Level: 1
DIST-CO-RTE-PM: 05-SLO-41,46-44.5/45.3,54.0/57.8
Work Description: Wye Segment - Route 41/46 Separation
Location Description:
Contractor Name: Atkinson Construction
Contractor Address: 18201 Von Karman - Suite 800, Irvine, CA 92612
Resident Engineer: Brian Harrington Structure Rep.: Dave Lewis
DIME Sample ID: 2024-07-26-41
TL Number from the TL Form:
Sample Submitted By Organization: CT D05 - Whitley Gardens Field Laboratory
Sample Organization Contact: 805-540-9933
Type of Sample: Acceptance
Type of Material: Concrete
Sample Taken Date: 07/26/2024
Date that the sample was received by the laboratory/organization performing the testing: 07/27/2024
The quantity of what the sample constitutes: LCB -552 Cubic yards
A brief description of the sample: 6X12 LCB Cylinders
From where was the sample collected: Manufacturer
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Atkinson Mobile Plant
The concrete mix design number: 12452-LCB-1
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: NA
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Loader
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2024-07-26-41-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 08/05/2024
Date Tested: 08/02/2024
Submitted By Organization: CT D05 - Whitley Gardens Field Laboratory
Organization Address: 102 South Whitley Gardens Drive,
Organization City: Paso Robles
Organization State: CA
Organization Zipcode: 93346
Organization Email: kyle.engen@dot.ca.gov
Organization Phone: (805) 540-9933
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
6.00 in
|
|
Average diameter of cylinder 2
|
6.00 in
|
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
|
Compressive strength (to nearest 10 psi)
|
600 psi
|
|
Maximum load on cylinder 1
|
16631 lb
|
|
Maximum load on cylinder 2
|
17145 lb
|
|
Compressive strength of cylinder 1
|
588.3 psi
|
|
Type of fracture pattern of cylinder 1
|
4
|
|
Compressive strength of cylinder 2
|
606.5 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Age of specimen
|
7 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2024-07-26-41-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 08/05/2024
Date Tested: 08/02/2024
Submitted By Organization: CT D05 - Whitley Gardens Field Laboratory
Organization Address: 102 South Whitley Gardens Drive,
Organization City: Paso Robles
Organization State: CA
Organization Zipcode: 93346
Organization Email: kyle.engen@dot.ca.gov
Organization Phone: (805) 540-9933
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
6.00 in
|
|
Average diameter of cylinder 2
|
6.00 in
|
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
|
Compressive strength (to nearest 10 psi)
|
620 psi
|
|
Maximum load on cylinder 1
|
17449 lb
|
|
Maximum load on cylinder 2
|
17887 lb
|
|
Compressive strength of cylinder 1
|
617.2 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
632.7 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Age of specimen
|
7 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2024-07-26-41-3
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 08/05/2024
Date Tested: 08/02/2024
Submitted By Organization: CT D05 - Whitley Gardens Field Laboratory
Organization Address: 102 South Whitley Gardens Drive,
Organization City: Paso Robles
Organization State: CA
Organization Zipcode: 93346
Organization Email: kyle.engen@dot.ca.gov
Organization Phone: (805) 540-9933
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
6.00 in
|
|
Average diameter of cylinder 2
|
6.00 in
|
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
|
Compressive strength (to nearest 10 psi)
|
650 psi
|
|
Maximum load on cylinder 1
|
18247 lb
|
|
Maximum load on cylinder 2
|
18502 lb
|
|
Compressive strength of cylinder 1
|
645.5 psi
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Compressive strength of cylinder 2
|
654.5 psi
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Age of specimen
|
7 days
|
|
Age of specimen in hours
|
no data0 hours
|