Sample Record for 2024-07-30-10

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 1000409 DEA: 051S1604 EFIS: 0524000176 QA Service Level: 1
DIST-CO-RTE-PM: 05-MON-1-60
Work Description: Rocky Creek Slip Out Permanent Restoration Project
Location Description:
Contractor Name: Gordon N Ball, Inc. (Fred Velasco/Stuart Yamamoto)
Contractor Address: 333 Camille Avenue, Alamo, CA 94507
Resident Engineer: Jorge Uberhuaga Structure Rep.: Daniel Dait

Sample Information

DIME Sample ID: 2024-07-30-10
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Bay Area Field Office
Sample Organization Contact: (916) 284-6784
Type of Sample: Quality Assurance
Type of Material: SMTL TM4 - Prestressing Strand
Sample Taken Date: 07/30/2024
Date that the sample was received by the laboratory/organization performing the testing: 08/02/2024
The quantity of what the sample constitutes: 1
A brief description of the sample: 0.6 L/R 7 Wire strand
From where was the sample collected: Manufacturer
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Sumiden Wire

Material Information

Comments:
Reel/Coil/Pack Number(s): T350128-2D, T350131-1, T350131-2, T350131-3, T350131-4, T350131-5, T350131-8
Number of Coils: 7
Group Number:
Strand Diameter: .6 in
Grade: 270
Strand Specification: ASTM A 416
Heat Number(s): T1366459
Mfg. Lot Number(s): T350128-2D, 1, 2, 3, 4, 5, 8
Manufacturer(s): Sumiden Wire

Test Results

Test 1 of 1

DIME Test ID: 2024-07-30-10-1
Test Method: ASTM A416-18: Standard Specification for Low-Relaxation, Seven-Wire Steel Strand for Prestressed Concrete
Verified Date: 08/28/2024
Date Tested: 08/05/2024
Submitted By Organization: WSP USA - San Diego
Organization Address: 690 Walnut Avenue,
Organization City: Vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: aaron.franklin@dot.ca.gov
Organization Phone: (858) 699-0513
General Comments for this Test: Chord Modulus not tested. Elongation reported in %: 6.3%, 6.5%, 6.3%, 6.4%, 3.8%, 5.4%, 6.1%
Test Result Compliance: complies
Additional Comments When Verified:
Number of Samples 7
Heat NumberCoilArea (sqin)Peak Load (lbf)Load at EUL (lbf)Chord Modulus (Msi)Elongation (in)Tested By
T1366459T350128-2.212602405381000Michael Gibson
T1366459T350131-2.212607945412000Michael Gibson
T1366459T350131-3.212605495302000Michael Gibson
T1366459T350131-1.213604275338500Michael Gibson
T1366459T350131-4.211591605320000Michael Gibson
T1366459T350131-5.211600005283000Michael Gibson
T1366459T350131-8.212600605320200Michael Gibson
UTM 120KIP
Temperature 72 f
Extensometers NA