Project Information
Project ID: 212470 DEA: 044A1304 EFIS: 0400001106 COOP: 042718
QA Service Level: 1
DIST-CO-RTE-PM: 04-SON-101-18.5/18.5
Work Description: CONSISTS OF MODIFICATION AND RECONSTRUCTION OF THE EXISTING US 101/HEARN AVENUE INTERCHANGE IN SONOMA COUNTY, INCLUDING REPLACING THE EXISTING TWO-LANE HEARN AVENUE OVERCROSSING WITH A NEW OVERCROSSING, AND MODIFYING THE SOUTHBOUND OFF-RAMP IN CITY
Location Description: IN SONOMA COUNTY.
Contractor Name: Ghilotti Construction Company, Inc. (Chase McPhaul)
Contractor Address: 246 Ghilotti Avenue, Santa Rosa, CA 95407
Resident Engineer: Seyed "Syd" Valeh Structure Rep.: Anthony "Tony" Tierra; Sardar Chalabe
Sample Information
DIME Sample ID: 2024-07-17-2
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Los Angeles Field Office
Sample Organization Contact: (858) 285-5797
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Welded Hoops
Sample Taken Date: 07/17/2024
Date that the sample was received by the laboratory/organization performing the testing: 07/19/2024
The quantity of what the sample constitutes: 436
A brief description of the sample: 4-8" Dia #7 Hoops
From where was the sample collected: Fabricator
Laboratory sample identification: Cal Trans Lab
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Martinez steel
Material Information
Production or Authorization Testing: Production Testing
Service or Ultimate: Ultimate
Rebar Heat Number(s): 126824
Hoop Manufacturer Lot Number(s): Lots 1 and 2
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Size: #7
Diameter of Hoop: 4'-8"
Epoxy Coated: No
Epoxy Coating Color: NA
Rebar Manufacturer: Cascade
Welding Company: Martinez Steel Fontana
Coating Standards: Uncoated
Weld Type: Flash Welded
Test Results
Test 1 of 7
DIME Test ID: 2024-07-17-2-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 07/24/2024
Date Tested: 07/24/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Broke in Heat Affected Zone
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 1 | 1 | 7/22mm | 0.6 | 51171.55 | 85286 | Broke in Heat Affected Zone | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 2 of 7
DIME Test ID: 2024-07-17-2-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 07/24/2024
Date Tested: 07/24/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 2 | 1 | 7/22mm | 0.6 | 52335.11 | 87225 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 3 of 7
DIME Test ID: 2024-07-17-2-3
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 07/24/2024
Date Tested: 07/24/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 3 | 1 | 7/22mm | 0.6 | 53022.00 | 88370 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 4 of 7
DIME Test ID: 2024-07-17-2-4
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 07/24/2024
Date Tested: 07/24/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 4 | 1 | 7/22mm | 0.6 | 51689.22 | 86149 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 5 of 7
DIME Test ID: 2024-07-17-2-5
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 07/24/2024
Date Tested: 07/24/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 1 | 2 | 7/22mm | 0.6 | 52761.00 | 87935 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 6 of 7
DIME Test ID: 2024-07-17-2-6
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 07/24/2024
Date Tested: 07/24/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 2 | 2 | 7/22mm | 0.6 | 52705.77 | 87843 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 7 of 7
DIME Test ID: 2024-07-17-2-7
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 07/24/2024
Date Tested: 07/24/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 3 | 2 | 7/22mm | 0.6 | 53093.55 | 88489 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|