Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 993409 DEA: 07327604 EFIS: 0716000132
QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-39-32.2/38.4
Work Description: INSTALL GUARDRAILS AND CONSTRUCT RETAINING WALLS.
Location Description: LOS ANGELES COUNTY NEAR AZUSA AT VARIOUS LOCATIONS FROM 0.3 MILE SOUTH OF NORTH FORK SAN GABRIEL RIVER OVERCROSSING TO 0.3 MILE NORTH CRYSTAL LAKE ROAD
Contractor Name: Bosco Inc
Contractor Address: 21353 Mayall St, Chatsworth, CA 91311
Resident Engineer: JOE DOUGHLY Structure Rep.: Nelson Parada
DIME Sample ID: 2024-07-08-51
TL Number from the TL Form: 07-327604-03
Sample Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Sample Organization Contact: (213) 817-0387
Type of Sample: Acceptance
Type of Material: Concrete
Sample Taken Date: 07/08/2024
Date that the sample was received by the laboratory/organization performing the testing: 07/10/2024
The quantity of what the sample constitutes: 130 CY
A brief description of the sample: 4X8 PCC cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 24-170
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Robertsons Redlands
The concrete mix design number: SC675B34
The truck number from where the sample was collected: 1
The batch plant ticket number from where the sample was collected: NA
Concrete batch plant: Robertsons Redlands
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: truck chute
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2024-07-08-51-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 07/15/2024
Date Tested: 07/15/2024
Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Organization Address: 1940 South Workman Mill Road,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90601
Organization Email: chad.chotibhongs@dot.ca.gov
Organization Phone: (213) 407-6963
General Comments for this Test:
Test Result Compliance: not applicable
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
4.03 in
|
|
Average diameter of cylinder 2
|
4.03 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.76 in^2
|
|
Cross sectional area of cylinder 2
|
12.76 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
3600 psi
|
|
Maximum load on cylinder 1
|
46684 lb
|
|
Maximum load on cylinder 2
|
45944 lb
|
|
Maximum load on cylinder 3
|
44340 lb
|
|
Compressive strength of cylinder 1
|
3658.6 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
3600.6 psi
|
|
Compressive strength of cylinder 3
|
3527.4 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Type of fracture pattern of cylinder 3
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
7 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2024-07-08-51-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Organization Address: 1940 South Workman Mill Road,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90601
Organization Email: chad.chotibhongs@dot.ca.gov
Organization Phone: (213) 407-6963
Data has not been verified.