Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 995217 DEA: 061F6904 EFIS: 0623000144
QA Service Level: 1
DIST-CO-RTE-PM: 06-TUL-190-38/57, 39/47, 32/57
Work Description: Emergency Landslide Repair. Roadway / Slope / Culvert repairs.
Location Description:
Contractor Name: MCM CONSTRUCTION
Contractor Address: 6413 32nd Street, North Highlands, Ca 95660
Resident Engineer: Javier Huerta Structure Rep.: Ramandeep Guraya
DIME Sample ID: 2024-06-17-82
TL Number from the TL Form:
Sample Submitted By Organization: CT D06 - Bakersfield Field Laboratory
Sample Organization Contact: 661-549-8281
Type of Sample: Acceptance
Type of Material: Concrete
Sample Taken Date: 06/17/2024
Date that the sample was received by the laboratory/organization performing the testing: 06/18/2024
The quantity of what the sample constitutes: Unknown Quantity
A brief description of the sample: PCC cylinders retaining wall
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Collected at jobsite
The concrete mix design number: 185811
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: Unknown
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Back of Truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2024-06-17-82-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 06/24/2024
Date Tested: 06/24/2024
Submitted By Organization: CT D06 - Bakersfield Field Laboratory
Organization Address: 1824 Norris Road,
Organization City: Bakersfield
Organization State: CA
Organization Zipcode: 93308
Organization Email: kulwinder.rai@dot.ca.gov
Organization Phone: (661) 549-8281
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
3980 psi
|
|
Maximum load on cylinder 1
|
48322 lb
|
|
Maximum load on cylinder 2
|
49961 lb
|
|
Maximum load on cylinder 3
|
51871 lb
|
|
Compressive strength of cylinder 1
|
3844.2 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
3974.6 psi
|
|
Compressive strength of cylinder 3
|
4126.6 psi
|
|
Type of fracture pattern of cylinder 2
|
4
|
|
Type of fracture pattern of cylinder 3
|
3
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
0
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
7 days
|
|
Age of specimen in hours
|
no data
|
DIME Test ID: 2024-06-17-82-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 07/15/2024
Date Tested: 07/15/2024
Submitted By Organization: CT D06 - Bakersfield Field Laboratory
Organization Address: 1824 Norris Road,
Organization City: Bakersfield
Organization State: CA
Organization Zipcode: 93308
Organization Email: kulwinder.rai@dot.ca.gov
Organization Phone: (661) 549-8281
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4820 psi
|
|
Maximum load on cylinder 1
|
61124 lb
|
|
Maximum load on cylinder 2
|
58491 lb
|
|
Maximum load on cylinder 3
|
62101 lb
|
|
Compressive strength of cylinder 1
|
4862.7 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
4653.2 psi
|
|
Compressive strength of cylinder 3
|
4940.4 psi
|
|
Type of fracture pattern of cylinder 2
|
1
|
|
Type of fracture pattern of cylinder 3
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
28 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2024-06-17-82-3
Test Method: CTM 521-June 2012: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 08/09/2024
Date Tested: 07/15/2024
Submitted By Organization: CT D06 - Bakersfield Field Laboratory
Organization Address: 1824 Norris Road,
Organization City: Bakersfield
Organization State: CA
Organization Zipcode: 93308
Organization Email: kulwinder.rai@dot.ca.gov
Organization Phone: (661) 549-8281
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Number of specimens
|
3
|
|
Average Compressive Strength (to nearest 10)
|
4820 lb/in^2
|
|
Cylinder Age
|
28 days
|
|
Break Description of Cylinder 1 (if not 'cone')
|
2
|
|
Break Description of Cylinder 2 (if not 'cone')
|
1
|
|
Break Description of Cylinder 3 (if not 'cone')
|
2
|