Print Report | Back to Sample Detail

Sample Record for 2024-06-13-1

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 994109 DEA: 060W1704 EFIS: 0617000103 QA Service Level: 1
DIST-CO-RTE-PM: 06-FRE-41-R27.4/R28.5
Work Description: REMOVE AC PAVEMENT, WIDEN TRAVEL WAY, AND CONSTRUCT RETAINING WALL.
Location Description: FRESNO COUNTY IN FRESNO FROM 0.1 MILE SOUTH OF ASHLAN AVENUE OVERCROSSING TO SHAW AVENUE OVERCROSSING
Contractor Name: RNR Construction, Inc
Contractor Address: 8589 Thys Court, Sacramento, CA,95828
Resident Engineer: Mark Mengoni Structure Rep.: Benjamin Holton

Sample Information

DIME Sample ID: 2024-06-13-1
TL Number from the TL Form:
Sample Submitted By Organization: CT D06 - Millbrook Field Laboratory
Sample Organization Contact: (559) 341-3953
Type of Sample: Acceptance
Type of Material: Concrete
Sample Taken Date: 06/13/2024
Date that the sample was received by the laboratory/organization performing the testing: 06/13/2024
The quantity of what the sample constitutes: 0-1000 Cy @ 19 Cy
A brief description of the sample: Concrete beams
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: RNR Construction

Material Information

The concrete mix design number: ND15518C
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 1358173
Concrete batch plant: Builders Sanger
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: STA : 1481+60-1481+78
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 3

DIME Test ID: 2024-06-13-1-1
Test Method: CTM 523-May 2020: Method of Test for Flexural Strength of Concrete
Verified Date: 06/26/2024
Date Tested: 06/26/2024
Submitted By Organization: CT D06 - Millbrook Field Laboratory
Organization Address: 1352 W. Olive Ave,
Organization City: Fresno
Organization State: CA
Organization Zipcode: 93728
Organization Email: tomas.silva@dot.ca.gov
Organization Phone: (559) 417-5341
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Number of specimens 3
Unit system used? US Units
Does the testing machine measure load or stress on the beam specimen? Load
Fracture initiates in the tension surface Within the Middle Third of the Span Length
Is a beam dimensional correction factor used? No
Modulus of rupture average 670 psi
Modulus of rupture 660 psi
Modulus of rupture 2 690 psi
Modulus of rupture 3 655 psi
Age of specimen 13 days

Test 2 of 3

DIME Test ID: 2024-06-13-1-2
Test Method: CTM 523-May 2020: Method of Test for Flexural Strength of Concrete
Verified Date: 07/11/2024
Date Tested: 07/11/2024
Submitted By Organization: CT D06 - Millbrook Field Laboratory
Organization Address: 1352 W. Olive Ave,
Organization City: Fresno
Organization State: CA
Organization Zipcode: 93728
Organization Email: tomas.silva@dot.ca.gov
Organization Phone: (559) 417-5341
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Number of specimens 3
Unit system used? US Units
Does the testing machine measure load or stress on the beam specimen? Load
Fracture initiates in the tension surface Within the Middle Third of the Span Length
Is a beam dimensional correction factor used? No
Modulus of rupture average 690 psi
Modulus of rupture 760 psi
Modulus of rupture 2 645 psi
Modulus of rupture 3 660 psi
Age of specimen 28 days

Test 3 of 3

DIME Test ID: 2024-06-13-1-3
Test Method: CTM 523-May 2020: Method of Test for Flexural Strength of Concrete
Verified Date: 07/13/2024
Date Tested: 07/13/2024
Submitted By Organization: CT D06 - Millbrook Field Laboratory
Organization Address: 1352 W. Olive Ave,
Organization City: Fresno
Organization State: CA
Organization Zipcode: 93728
Organization Email: tomas.silva@dot.ca.gov
Organization Phone: (559) 417-5341
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Number of specimens 3
Unit system used? US Units
Does the testing machine measure load or stress on the beam specimen? Load
Fracture initiates in the tension surface Within the Middle Third of the Span Length
Is a beam dimensional correction factor used? No
Modulus of rupture average 680 psi
Modulus of rupture 675 psi
Modulus of rupture 2 635 psi
Modulus of rupture 3 735 psi
Age of specimen 30 days