Project Information

Project ID: 209217 DEA: 080F5404 EFIS: 0800000136 COOP: 081468 QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-91,15-0.0/13.04, 35.64/45.14
Work Description: SR-91 Corridor Improvement Project: Develop approx. 8 miles of tolled express lanes and related improvements within SR 91 between the Riverside/Orange County line and I-15, including transition areas.
Location Description: 08-RIV-91-0.0/13.04; 12-ORA-91-R14.43/R18.91; 08-RIV-15-35.64/45.14
Contractor Name: Atkinson Walsh, Joint Venture
Contractor Address: 1785 Sampson Ave, Corona, CA 92879
Resident Engineer: Richard Hebert Structure Rep.: Cyrus Shahinpar

Sample Information

DIME Sample ID: 2016-10-13-2
TL Number from the TL Form: SRL332
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 10/13/2016
Date that the sample was received by the laboratory/organization performing the testing: 10/18/2016
The quantity of what the sample constitutes: 8
A brief description of the sample: 6x12 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 888-SRL332
Structure unique identifier: NP
Structure name: Unknown
The fabricator/manufacturer/facility name: Holliday Rock Chino

Material Information

The concrete mix design number: CM5635
The truck number from where the sample was collected: 286
The batch plant ticket number from where the sample was collected: 118054323
Concrete batch plant: NP
The fabricator/manufacturer designation for the sample: NP
A detailed description of where the material sample was collected: LOAD 8
Where the material sample would have been placed if not sampled: br 24 abut 1 approach
From Lot No.: NP
Bag Lot No.: Unknown

Test Results

Test 1 of 4

DIME Test ID: 2016-10-13-2-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 10/20/2016
Date Tested: 10/20/2016
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 6.04 in
Average diameter of cylinder 2 6.04 in
Cross sectional area of cylinder 1 28.65 in^2
Cross sectional area of cylinder 2 28.65 in^2
Compressive strength (to nearest 10 psi) 3780 psi
Maximum load on cylinder 1 107340 lb
Maximum load on cylinder 2 109490 lb
Compressive strength of cylinder 1 3746.6 psi
Type of fracture pattern of cylinder 1 3
Compressive strength of cylinder 2 3821.6 psi
Type of fracture pattern of cylinder 2 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 no data
Age of specimen 7 days
Age of specimen in hours no data

Test 2 of 4

DIME Test ID: 2016-10-13-2-2
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 10/24/2016
Date Tested: 10/23/2016
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 6.03 in
Average diameter of cylinder 2 6.04 in
Cross sectional area of cylinder 1 28.56 in^2
Cross sectional area of cylinder 2 28.65 in^2
Compressive strength (to nearest 10 psi) 4310 psi
Maximum load on cylinder 1 121360 lb
Maximum load on cylinder 2 125380 lb
Compressive strength of cylinder 1 4249.3 psi
Type of fracture pattern of cylinder 1 1
Compressive strength of cylinder 2 4376.3 psi
Type of fracture pattern of cylinder 2 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 no data
Age of specimen 11 days
Age of specimen in hours no data

Test 3 of 4

DIME Test ID: 2016-10-13-2-3
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 11/03/2016
Date Tested: 10/27/2016
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 6.03 in
Average diameter of cylinder 2 6.03 in
Cross sectional area of cylinder 1 28.56 in^2
Cross sectional area of cylinder 2 28.56 in^2
Compressive strength (to nearest 10 psi) 4520 psi
Maximum load on cylinder 1 131210 lb
Maximum load on cylinder 2 127040 lb
Compressive strength of cylinder 1 4594.2 psi
Type of fracture pattern of cylinder 1 2
Compressive strength of cylinder 2 4448.2 psi
Type of fracture pattern of cylinder 2 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 no data
Age of specimen 14 days
Age of specimen in hours no data

Test 4 of 4

DIME Test ID: 2016-10-13-2-4
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 11/10/2016
Date Tested: 11/10/2016
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 6.03 in
Average diameter of cylinder 2 6.03 in
Cross sectional area of cylinder 1 28.56 in^2
Cross sectional area of cylinder 2 28.56 in^2
Compressive strength (to nearest 10 psi) 5380 psi
Maximum load on cylinder 1 155160 lb
Maximum load on cylinder 2 151910 lb
Compressive strength of cylinder 1 5432.8 psi
Type of fracture pattern of cylinder 1 1
Compressive strength of cylinder 2 5319.0 psi
Type of fracture pattern of cylinder 2 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 no data
Age of specimen 28 days
Age of specimen in hours no data