Project ID: 994121 DEA: 120P68U4 EFIS: 1218000105
QA Service Level: 1
DIST-CO-RTE-PM: 12-ORA-1-13.0/33.7
Work Description: COLD PLANE, PLACE RHMA AND MODIFY CURB RAMPS AND ELECTRICAL SYSTEMS.
Location Description: ORANGE COUNTY AT VARIOUS LOCATIONS FROM CRYSTAL HEIGHTS DRIVE TO LOS ANGELES/ORANGE COUNTY LINE
Contractor Name: CHUMO CONSTRUCTION INC.
Contractor Address: 4949 2nd St., Fallbrook, CA 92028
Resident Engineer: Christopher Blanco Structure Rep.: Vian Ghazi
DIME Sample ID: 2024-05-09-67
TL Number from the TL Form:
Sample Submitted By Organization: CT D12 - Huntington Beach Field Laboratory
Sample Organization Contact: 9492798846
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 05/09/2024
Date that the sample was received by the laboratory/organization performing the testing: 05/10/2024
The quantity of what the sample constitutes: 6
A brief description of the sample: 4x8 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 24-0202
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Robertson's
The concrete mix design number: 1610838
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 1
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Concrete from wheelbarrow
Where the material sample would have been placed if not sampled: Structural
From Lot No.:
Bag Lot No.:
DIME Test ID: 2024-05-09-67-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 05/24/2024
Date Tested: 05/23/2024
Submitted By Organization: CT D12 - Huntington Beach Field Laboratory
Organization Address: 19601 Beach Boulevard,
Organization City: Huntington Beach
Organization State: CA
Organization Zipcode: 92648
Organization Email: frank.mai@dot.ca.gov
Organization Phone: (949) 279-8846
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.01 in
|
|
Cross sectional area of cylinder 1
|
12.56 in^2
|
|
Cross sectional area of cylinder 2
|
12.56 in^2
|
|
Cross sectional area of cylinder 3
|
12.63 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4360 psi
|
|
Maximum load on cylinder 1
|
56880 lb
|
|
Maximum load on cylinder 2
|
51720 lb
|
|
Maximum load on cylinder 3
|
55870 lb
|
|
Type of fracture pattern of cylinder 1
|
5
|
|
Type of fracture pattern of cylinder 2
|
5
|
|
Type of fracture pattern of cylinder 3
|
5
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
14 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2024-05-09-67-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 06/06/2024
Date Tested: 06/06/2024
Submitted By Organization: CT D12 - Huntington Beach Field Laboratory
Organization Address: 19601 Beach Boulevard,
Organization City: Huntington Beach
Organization State: CA
Organization Zipcode: 92648
Organization Email: frank.mai@dot.ca.gov
Organization Phone: (949) 279-8846
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.01 in
|
|
Average diameter of cylinder 3
|
4.01 in
|
|
Cross sectional area of cylinder 1
|
12.56 in^2
|
|
Cross sectional area of cylinder 2
|
12.62 in^2
|
|
Cross sectional area of cylinder 3
|
12.62 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4930 psi
|
|
Maximum load on cylinder 1
|
57140 lb
|
|
Maximum load on cylinder 2
|
60470 lb
|
|
Maximum load on cylinder 3
|
68770 lb
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Type of fracture pattern of cylinder 3
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
28 days
|
|
Age of specimen in hours
|
no data0 hours
|