Sample Record for 2016-09-16-11
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 208945 DEA: 07288604 EFIS: 0700021080 COOP: 074663
QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-710-6.0-9.4
Work Description: Gerald Desmond Bridge Replacement - A Design Build project. IQA samples will be selected by Port/Caltrans representatives and sent to Translab for testing.
Location Description: Port of Long Beach (District 7)
Contractor Name: Shimmick/FCC/Impregilo (SFI) JV
Contractor Address: 11 Golden Shore, Suite 330, Long Beach, CA 90802
Resident Engineer: Structure Rep.: Sami Deeb
Sample Information
DIME Sample ID: 2016-09-16-11
TL Number from the TL Form: 0916160D-Tower 17
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 09/16/2016
Date that the sample was received by the laboratory/organization performing the testing: 09/21/2016
The quantity of what the sample constitutes: 2
A brief description of the sample: concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 866-60D
Structure unique identifier: Unknown
Structure name: Unknown
The fabricator/manufacturer/facility name: A and A
Material Information
The concrete mix design number: sfi scc
The truck number from where the sample was collected: 0427
The batch plant ticket number from where the sample was collected: 19010452
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: Unknown
A detailed description of where the material sample was collected: chute
Where the material sample would have been placed if not sampled: lift 12 elev 211 54 to 224 54
From Lot No.: Unknown
Bag Lot No.: Unknown
Test Results
Test 1 of 2
DIME Test ID: 2016-09-16-11-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 10/14/2016
Date Tested: 10/14/2016
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Average diameter of cylinder 1
|
6.02 in
|
Average diameter of cylinder 2
|
6.02 in
|
Cross sectional area of cylinder 1
|
28.46 in^2
|
Cross sectional area of cylinder 2
|
28.46 in^2
|
Compressive strength (to nearest 10 psi)
|
8900 psi
|
Maximum load on cylinder 1
|
252820 lb
|
Maximum load on cylinder 2
|
253850 lb
|
Compressive strength of cylinder 1
|
8883.3 psi
|
Type of fracture pattern of cylinder 1
|
3
|
Compressive strength of cylinder 2
|
8919.5 psi
|
Type of fracture pattern of cylinder 2
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
no data
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
no data
|
Test 2 of 2
DIME Test ID: 2016-09-16-11-2
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 10/28/2016
Date Tested: 10/28/2016
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Average diameter of cylinder 1
|
6.01 in
|
Average diameter of cylinder 2
|
6.02 in
|
Cross sectional area of cylinder 1
|
28.37 in^2
|
Cross sectional area of cylinder 2
|
28.46 in^2
|
Compressive strength (to nearest 10 psi)
|
9790 psi
|
Maximum load on cylinder 1
|
275090 lb
|
Maximum load on cylinder 2
|
281320 lb
|
Compressive strength of cylinder 1
|
9696.5 psi
|
Type of fracture pattern of cylinder 1
|
1
|
Compressive strength of cylinder 2
|
9884.8 psi
|
Type of fracture pattern of cylinder 2
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
no data
|
Age of specimen
|
42 days
|
Age of specimen in hours
|
no data
|