Project ID: 994351 DEA: 07322004 EFIS: 0716000053
QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-118-R11.0/R14.0
Work Description: CONSTRUCT STORMWATER TREATMENT DEVICES.
Location Description: THE CITY AND COUNTY OF LOS ANGELES FROM 0.1 MILE WEST OF ARLETA AVENUE UNDERCROSSING TO 0.1 MILE WEST OF ROUTE 118/210 SEPARATION
Contractor Name: G&G Electric Inc.
Contractor Address: 4229 Giles Ct., Riverside, CA 92503
Resident Engineer: Wassem Bakhet Structure Rep.: Unknown
DIME Sample ID: 2024-04-08-67
TL Number from the TL Form: 040824
Sample Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Sample Organization Contact: (213) 817-0387
Type of Sample: Department Acceptance
Type of Material: Concrete
Sample Taken Date: 04/08/2024
Date that the sample was received by the laboratory/organization performing the testing: 04/15/2024
The quantity of what the sample constitutes: 130 CY
A brief description of the sample: 6X12 PCC cylinder
From where was the sample collected: Job Site
Laboratory sample identification: 24-054
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: National Ready Mix Concrete Company
The concrete mix design number: S63C451T1
The truck number from where the sample was collected: 3
The batch plant ticket number from where the sample was collected: 713013
Concrete batch plant: National Ready Mix Concrete
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: truck chute
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2024-04-08-67-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 04/22/2024
Date Tested: 04/15/2024
Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Organization Address: 1940 South Workman Mill Road,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90601
Organization Email: chad.chotibhongs@dot.ca.gov
Organization Phone: (213) 407-6963
General Comments for this Test:
Test Result Compliance: not applicable
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
1
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
5.98 in
|
|
Cross sectional area of cylinder 1
|
28.09 in^2
|
|
Compressive strength of cylinder (to nearest 10 psi)
|
2600 psi
|
|
Maximum load on cylinder 1
|
72982 lb
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Age of specimen
|
7 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2024-04-08-67-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 04/22/2024
Date Tested: 04/22/2024
Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Organization Address: 1940 South Workman Mill Road,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90601
Organization Email: chad.chotibhongs@dot.ca.gov
Organization Phone: (213) 407-6963
General Comments for this Test:
Test Result Compliance: not applicable
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
6.01 in
|
|
Average diameter of cylinder 2
|
6.00 in
|
|
Cross sectional area of cylinder 1
|
28.37 in^2
|
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
|
Compressive strength (to nearest 10 psi)
|
3260 psi
|
|
Maximum load on cylinder 1
|
88668 lb
|
|
Maximum load on cylinder 2
|
96134 lb
|
|
Compressive strength of cylinder 1
|
3125.4 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
3400.6 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Age of specimen
|
14 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2024-04-08-67-3
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 05/20/2024
Date Tested: 05/20/2024
Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Organization Address: 1940 South Workman Mill Road,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90601
Organization Email: chad.chotibhongs@dot.ca.gov
Organization Phone: (213) 407-6963
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
6.01 in
|
|
Average diameter of cylinder 2
|
6.00 in
|
|
Cross sectional area of cylinder 1
|
28.37 in^2
|
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4690 psi
|
|
Maximum load on cylinder 1
|
132308 lb
|
|
Maximum load on cylinder 2
|
133409 lb
|
|
Compressive strength of cylinder 1
|
4663.7 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
4719.1 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Age of specimen
|
42 days
|
|
Age of specimen in hours
|
no data0 hours
|