Project Information

Project ID: 995263 DEA: 061G3304 EFIS: 0624000029 QA Service Level: 1
DIST-CO-RTE-PM: 06-FRE-180-118/138
Work Description: FRE 180 Emergency Slope Repairs.
Location Description:
Contractor Name: CAL VALLEY CONSTRUCTION
Contractor Address: 5125 N. Gates Ave, Ste 102, Fresno, CA 93722
Resident Engineer: Mark Mengoni Structure Rep.: Benjamin Holton

Sample Information

DIME Sample ID: 2024-04-19-18
TL Number from the TL Form:
Sample Submitted By Organization: CT D06 - Millbrook Field Laboratory
Sample Organization Contact: (559) 341-3953
Type of Sample: Verification
Type of Material: Concrete
Sample Taken Date: 04/19/2024
Date that the sample was received by the laboratory/organization performing the testing: 04/23/2024
The quantity of what the sample constitutes: 19 CY
A brief description of the sample: PCC cylinders
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier: 06-1G3304, at PM 126.5
Structure name: Retaining Wall
The fabricator/manufacturer/facility name: Outback Materials, Fresno

Material Information

The concrete mix design number: 72T1X39
The truck number from where the sample was collected: 111
The batch plant ticket number from where the sample was collected: 158073
Concrete batch plant: Outback Materials
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Concrete Truck 111
Where the material sample would have been placed if not sampled: Concrete barrier rail at PM 126.5
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 2

DIME Test ID: 2024-04-19-18-1
Test Method: ASTM C231-17a: Standard Test Method for Air Content of Freshly Mixed Concrete by the Pressure Method
Submitted By Organization: CT D06 - Millbrook Field Laboratory
Organization Address: 1352 W. Olive Ave,
Organization City: Fresno
Organization State: CA
Organization Zipcode: 93728
Organization Email: tomas.silva@dot.ca.gov
Organization Phone: (559) 417-5341
Data has not been verified.

Test 2 of 2

DIME Test ID: 2024-04-19-18-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 05/20/2024
Date Tested: 05/17/2024
Submitted By Organization: CT D06 - Millbrook Field Laboratory
Organization Address: 1352 W. Olive Ave,
Organization City: Fresno
Organization State: CA
Organization Zipcode: 93728
Organization Email: tomas.silva@dot.ca.gov
Organization Phone: (559) 417-5341
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 3.99 in
Average diameter of cylinder 3 4.01 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.5 in^2
Cross sectional area of cylinder 3 12.63 in^2
Compressive strength (to nearest 10 psi) 4630 psi
Maximum load on cylinder 1 57390 lb
Maximum load on cylinder 2 57170 lb
Maximum load on cylinder 3 59920 lb
Compressive strength of cylinder 1 4565.6 psi
Type of fracture pattern of cylinder 1 2
Compressive strength of cylinder 2 4573.6 psi
Compressive strength of cylinder 3 4744.3 psi
Type of fracture pattern of cylinder 2 2
Type of fracture pattern of cylinder 3 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 28 days
Age of specimen in hours no data0 hours