Sample Record for 2024-02-20-7
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 993815 DEA: 081C0814 EFIS: 0816000086
QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-10-R60.7/R74.3
Work Description: I-10 PAVEMENT REHABILITATION (SEGMENT 1) PROJECT
Location Description: Coachella
Contractor Name: COFFMAN SPECIALTIES, INC
Contractor Address: 4375 JUTLAND DRIVE STE 260, SAN DIEGO CA 92117
Resident Engineer: Michael Sergah Structure Rep.: Al Alina
Sample Information
DIME Sample ID: 2024-02-20-7
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (530) 329-6527
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 02/20/2024
Date that the sample was received by the laboratory/organization performing the testing: 02/28/2024
The quantity of what the sample constitutes: 4
A brief description of the sample: D250 L Bar Lock Standard Coupler
From where was the sample collected: Manufacturer
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Dayton Superior
Material Information
Production or Authorization Testing: Production Testing
Service or Ultimate: Service
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: CMC
Coupler Manufacturer: Dayton Superior
Intermediate Assembler or Fabricator:
Rebar Size: #8
Coupler Model: D250L Bar Lock
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter:
Rebar Hoop Fabricator:
Coupler Component Heat/Lot Number(s): 4000003591
Rebar Heat Number(s): 9001339
Rebar Size 2 :
Coupler Unique ID: SL-17-06
Test Results
Test 1 of 3
DIME Test ID: 2024-02-20-7-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 03/05/2024
Date Tested: 03/05/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples Tested
|
1
|
| Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 1 | | No. 8/25mm | 1 | 0.0004 | 0.79 | 80442 | 101825 | Service Splice | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72.00 f
|
|
Halo ID
|
Small
|
Test 2 of 3
DIME Test ID: 2024-02-20-7-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 03/05/2024
Date Tested: 03/05/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples Tested
|
1
|
| Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 2 | | No. 8/25mm | 1 | 0 | 0.79 | 76910 | 97354 | Service Splice | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72.00 f
|
|
Halo ID
|
|
Test 3 of 3
DIME Test ID: 2024-02-20-7-3
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 03/05/2024
Date Tested: 03/05/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples Tested
|
1
|
| Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 3 | | No. 8/25mm | 1 | 0 | 0.79 | 82178 | 104022 | Service Splice | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72.00 f
|
|
Halo ID
|
|