Print Report | Back to Sample Detail

Sample Record for 2024-01-25-46

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 214355 DEA: 120K0214 EFIS: 1214000096 QA Service Level: 1
DIST-CO-RTE-PM: 12-ORA-5-12.4/14.5
Work Description: South County Improvement Project (Phase 1 - Avery/Crown Valley) PLACE HMA, INSTALL CONC PAVEMENT, RETAIN WALL, MODIFY ELECT SYS. | Add one lane btwn 73 & Oso PKWY
Location Description: ORANGE COUNTY IN SAN JUAN CAPISTRANO, LAGUNA HILLS, LAGUNA NIGUEL AND MISSION VIEJO FROM 0.5 MILE SOUTH OF AVERY PARKWAY UNDERCROSSING TO 0.8 MILE NORTH OF CROWN VALLEY PARKWAY OVERCROSSING
Contractor Name: ORTIZ ENTERPRISES, INC.
Contractor Address: 6 Cushing, Suite 200, Irvine, CA 92618
Resident Engineer: Artin Merati Structure Rep.: Imad Karam

Sample Information

DIME Sample ID: 2024-01-25-46
TL Number from the TL Form:
Sample Submitted By Organization: Sequoia Consultants
Sample Organization Contact: (714) 974-6316
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 01/25/2024
Date that the sample was received by the laboratory/organization performing the testing: 01/26/2024
The quantity of what the sample constitutes: 2 cylinders
A brief description of the sample: structural concrete
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Cemex Irvine

Material Information

The concrete mix design number: 1611681
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 31087726
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: I-5 NB RW 748 Pile #11 & #14
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 1

DIME Test ID: 2024-01-25-46-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 02/27/2024
Date Tested: 02/22/2024
Submitted By Organization: Sequoia Consultants
Organization Address: 361 West Grove Avenue,
Organization City: Orange
Organization State: CA
Organization Zipcode: 92865
Organization Email: sranjan@sequoiacon.com
Organization Phone: 1 (714) 974-6316
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 6.00 in
Average diameter of cylinder 2 6.00 in
Cross sectional area of cylinder 1 28.27 in^2
Cross sectional area of cylinder 2 28.27 in^2
Compressive strength (to nearest 10 psi) 4900 psi
Maximum load on cylinder 1 137674 lb
Maximum load on cylinder 2 139371 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 28 days
Age of specimen in hours no data0 hours