Project Information

Project ID: 215220 DEA: 07210624 EFIS: 0719000068 QA Service Level: 1
DIST-CO-RTE-PM: 07-LA,SBD-71-1.8/R4.7&R0.0/R0.2
Work Description: PLACE STRUCTURE CONCRETE RETAINING WALLS & BOX CULVERT AND PLACE JPCP.
Location Description: IN LOS ANGELES AND SAN BERNARDINO COUNTIES IN POMONA AND CHINO HILLS FROM 0.2 MILE SOUTH OF MISSION BOULEVARD OVERCROSSING TO 0.2 MILE OF SAN BERNARDINO COUNTY LINE.
Contractor Name: OHL USA
Contractor Address: 1920 Main Street, Suite 310, Irvine, California 92614
Resident Engineer: Michael Wang Structure Rep.: Ryan Valentine

Sample Information

DIME Sample ID: 2024-01-08-59
TL Number from the TL Form:
Sample Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Sample Organization Contact: (213) 817-0387
Type of Sample: Department Acceptance
Type of Material: Concrete
Sample Taken Date: 01/08/2024
Date that the sample was received by the laboratory/organization performing the testing: 01/09/2024
The quantity of what the sample constitutes: 100 cu. yd.
A brief description of the sample: JPCP beams
From where was the sample collected: Job Site
Laboratory sample identification: 24-0099
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Robertson's

Material Information

The concrete mix design number: LB060008
The truck number from where the sample was collected: 1729
The batch plant ticket number from where the sample was collected: 631453
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Sampled from chute of ready mix truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 2

DIME Test ID: 2024-01-08-59-1
Test Method: ASTM C78-18: Standard Test Method for Flexural Strength of Concrete (Using Simple Beam with Third-Point Loading)
Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Organization Address: 1940 South Workman Mill Road,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90601
Organization Email:
Organization Phone: (213) 817-0387
This test has been superseded on 02/05/2024. The corrected test ID is: 2024-01-08-59-2
Reason: retested

Test 2 of 2

DIME Test ID: 2024-01-08-59-2
Test Method: ASTM C78-18: Standard Test Method for Flexural Strength of Concrete (Using Simple Beam with Third-Point Loading)
Verified Date: 02/05/2024
Date Tested: 02/05/2024
Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Organization Address: 1940 South Workman Mill Road,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90601
Organization Email: chad.chotibhongs@dot.ca.gov
Organization Phone: (213) 817-0387
General Comments for this Test:
The test was superseded from test ID: 2024-01-08-59-1
Test Result Compliance:
Additional Comments When Verified:
Number of specimens 3
Unit system used? US Units
Does the testing machine measure load or stress on the beam specimen? Load
Fracture initiates in the tension surface Within the Middle Third of the Span Length
Is a beam dimensional correction factor used? No
Modulus of rupture 715 psi
Modulus of rupture 2 655 psi
Modulus of rupture 3 700 psi
Modulus of rupture average 690 psi