Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 994803 DEA: 043J0704 EFIS: 0415000077
QA Service Level: 1
DIST-CO-RTE-PM: 04-CC-80-10.1/13.5
Work Description: Remove PCC and AC, place PCP and AC Resurfacing.
Location Description: Construction on State Highway in Contra Costa County in Hercules and Crockett from Route 80/4 separation to 0.1 mile west of Crockett Viaduct.
Contractor Name: VANGUARD CONSTRUCTION, INC.
Contractor Address: 651 ENTERPRISE CT, LIVERMORE, CA 94550
Resident Engineer: Ta Seng Structure Rep.: Unknown
DIME Sample ID: 2023-11-09-108
TL Number from the TL Form:
Sample Submitted By Organization: CT D04 - Concord Field Laboratory
Sample Organization Contact: (510) 714-7019
Type of Sample: Quality Assurance
Type of Material: Hot Mix Asphalt
Sample Taken Date: 11/09/2023
Date that the sample was received by the laboratory/organization performing the testing: 12/21/2023
The quantity of what the sample constitutes: 750 Tons
A brief description of the sample: 1/2" HMA
From where was the sample collected: Supplier
Laboratory sample identification: Rich_24_007
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: County Asphalt Martinez
DIME Test ID: 2023-11-09-108-1
Test Method: AASHTO T308-10: Standard Method of Test for Determining the Asphalt Binder Content of Hot Mix Asphalt (HMA) by the Ignition Method (Method A) (Asphalt Binder Content)
Verified Date: 02/05/2024
Date Tested: 01/11/2024
Submitted By Organization: CT D04 - Concord Field Laboratory
Organization Address: 2525 Stanwell Drive, Suite 100,
Organization City: Concord
Organization State: CA
Organization Zipcode: 94520
Organization Email: gurind.joshi@dot.ca.gov
Organization Phone: (510) 714-7019
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
What temperature unit is used?
|
Celsius
|
|
Test procedure used?
|
Method A
|
|
Mass of HMA Sample prior to ignition
|
1588.3 g
|
|
Corrected Asphalt Binder Content
|
5.09 %
|
|
Mass Loss
|
110.7 g
|
|
Correction Factor (Percent by mass of HMA Specimen)
|
1.69 %
|
|
Moisture Content
|
no data0 %
|
|
Temperature Compensation Factor
|
0.19 %
|
|
Test Temperature
|
538 C
|