Sample Record for 2023-12-29-1
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 994820 DEA: 060V1104 EFIS: 0616000208
QA Service Level: 1
DIST-CO-RTE-PM: 06-FRE,KIN-5,41,198-Var
Work Description: STRATFORD KINGS RIVER BRIDGE REPLACEMENT.
Location Description: FRESNO AND KINGS COUNTIES AT VARIOUS LOCATIONS
Contractor Name: M.C.M. Construction, INC. (Richard McCall)
Contractor Address: 6413 32nd Street, North Highlands, Ca 95660
Resident Engineer: Din Dadawalla Structure Rep.: Martin Garcia
Sample Information
DIME Sample ID: 2023-12-29-1
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Los Angeles Field Office
Sample Organization Contact: (858) 285-5797
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Welded Hoops
Sample Taken Date: 12/29/2023
Date that the sample was received by the laboratory/organization performing the testing: 01/03/2024
The quantity of what the sample constitutes: 3198
A brief description of the sample: #6 2'-4"
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: TNT Rebar
Material Information
Production or Authorization Testing: Production Testing
Service or Ultimate: Ultimate
Rebar Heat Number(s): 1202055162
Hoop Manufacturer Lot Number(s): 1-22
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Size: #6
Diameter of Hoop: 2'-4"
Epoxy Coated: No
Epoxy Coating Color: NA
Rebar Manufacturer: NUCOR
Welding Company: TNT Rebar
Coating Standards: Uncoated
Weld Type: Flash Welded
Test Results
Test 1 of 18
DIME Test ID: 2023-12-29-1-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brian.ellis@dot.ca.gov
Organization Phone: (916) 380-8623
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 1 | 1 | 6/19mm | 0.44 | 40006.03 | 90923 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 2 of 18
DIME Test ID: 2023-12-29-1-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brian.ellis@dot.ca.gov
Organization Phone: (916) 380-8623
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 2 | 1 | 6/19mm | 0.44 | 40038.46 | 90997 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 3 of 18
DIME Test ID: 2023-12-29-1-3
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brian.ellis@dot.ca.gov
Organization Phone: (916) 380-8623
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 3 | 1 | 6/19mm | 0.44 | 40062.46 | 91051 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 4 of 18
DIME Test ID: 2023-12-29-1-4
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brian.ellis@dot.ca.gov
Organization Phone: (916) 380-8623
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 1 | 6 | 6/19mm | 0.44 | 39959.91 | 90818 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 5 of 18
DIME Test ID: 2023-12-29-1-5
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brian.ellis@dot.ca.gov
Organization Phone: (916) 380-8623
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 2 | 6 | 6/19mm | 0.44 | 39829.67 | 90522 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 6 of 18
DIME Test ID: 2023-12-29-1-6
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brian.ellis@dot.ca.gov
Organization Phone: (916) 380-8623
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 3 | 6 | 6/19mm | 0.44 | 40150.81 | 91252 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 7 of 18
DIME Test ID: 2023-12-29-1-7
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brian.ellis@dot.ca.gov
Organization Phone: (916) 380-8623
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 1 | 11 | 6/19mm | 0.44 | 39717.98 | 90268 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 8 of 18
DIME Test ID: 2023-12-29-1-8
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brian.ellis@dot.ca.gov
Organization Phone: (916) 380-8623
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 2 | 11 | 6/19mm | 0.44 | 39782.62 | 90415 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 9 of 18
DIME Test ID: 2023-12-29-1-9
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brian.ellis@dot.ca.gov
Organization Phone: (916) 380-8623
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 3 | 11 | 6/19mm | 0.44 | 39838.10 | 90541 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 10 of 18
DIME Test ID: 2023-12-29-1-11
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brian.ellis@dot.ca.gov
Organization Phone: (916) 380-8623
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 1 | 16 | 6/19mm | 0.44 | 39464.22 | 89691 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 11 of 18
DIME Test ID: 2023-12-29-1-12
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brian.ellis@dot.ca.gov
Organization Phone: (916) 380-8623
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 2 | 16 | 6/19mm | 0.44 | 39798.77 | 90452 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 12 of 18
DIME Test ID: 2023-12-29-1-13
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brian.ellis@dot.ca.gov
Organization Phone: (916) 380-8623
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 3 | 16 | 6/19mm | 0.44 | 39777.27 | 90403 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 13 of 18
DIME Test ID: 2023-12-29-1-14
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brian.ellis@dot.ca.gov
Organization Phone: (916) 380-8623
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 1 | 20 | 6/19mm | 0.44 | 40076.56 | 91083 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 14 of 18
DIME Test ID: 2023-12-29-1-15
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brian.ellis@dot.ca.gov
Organization Phone: (916) 380-8623
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 2 | 20 | 6/19mm | 0.44 | 40071.00 | 91070 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 15 of 18
DIME Test ID: 2023-12-29-1-16
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brian.ellis@dot.ca.gov
Organization Phone: (916) 380-8623
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 3 | 20 | 6/19mm | 0.44 | 39887.45 | 90653 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 16 of 18
DIME Test ID: 2023-12-29-1-17
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brian.ellis@dot.ca.gov
Organization Phone: (916) 380-8623
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 1 | 22 | 6/19mm | 0.44 | 39828.08 | 90518 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 17 of 18
DIME Test ID: 2023-12-29-1-18
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brian.ellis@dot.ca.gov
Organization Phone: (916) 380-8623
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 2 | 22 | 6/19mm | 0.44 | 39946.84 | 90788 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|
Test 18 of 18
DIME Test ID: 2023-12-29-1-19
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile)
Verified Date: 01/04/2024
Date Tested: 01/04/2024
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brian.ellis@dot.ca.gov
Organization Phone: (916) 380-8623
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
1
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 3 | 22 | 6/19mm | 0.44 | 39804.31 | 90464 | Ok Necking | aauvinen |
| |
|
UTM
|
400kip
|
|
Temperature
|
72 f
|