Project ID: 993856 DEA: 042J7304 EFIS: 0415000004
QA Service Level: 1
DIST-CO-RTE-PM: 04-SM-101-6.7/7.6
Work Description: SM 101 Cordilleras Crk Br Replacement
Location Description:
Contractor Name: Myers & Sons Construction
Contractor Address: 45 Morrison Ave, Sacramento, CA 95838
Resident Engineer: Peter Lam Structure Rep.: Tyler Pinell
DIME Sample ID: 2023-09-11-95
TL Number from the TL Form:
Sample Submitted By Organization: Myers and Sons Construction
Sample Organization Contact: (650) 864-2057
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 09/11/2023
Date that the sample was received by the laboratory/organization performing the testing: 09/11/2023
The quantity of what the sample constitutes: 16 CY
A brief description of the sample: DOT Class 1 5000psi@28 days 4" slump 0.4 w/c ratio 1" agg
From where was the sample collected: Job Site
Laboratory sample identification: 432350
Structure unique identifier:
Structure name: 35-0019
The fabricator/manufacturer/facility name: Central Concrete Supply
The concrete mix design number: D101C5E1
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 432350
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Abutment 1
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2023-09-11-95-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/28/2023
Date Tested: 09/11/2023
Submitted By Organization: Myers and Sons Construction
Organization Address: 45 Morrison Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95838
Organization Email: vvincent@myers-sons.com
Organization Phone: (650) 864-2057
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
1
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C39 - Ground End
|
Average diameter of cylinder 1
|
8.00 in
|
Compressive strength of cylinder (to nearest 10 psi)
|
7780 psi
|
Maximum load on cylinder 1
|
97470 lb
|
Type of fracture pattern of cylinder 1
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
0
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
no data
|
DIME Test ID: 2023-09-11-95-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/28/2023
Date Tested: 09/12/2023
Submitted By Organization: Myers and Sons Construction
Organization Address: 45 Morrison Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95838
Organization Email: vvincent@myers-sons.com
Organization Phone: (650) 864-2057
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
1
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
Average diameter of cylinder 1
|
8.00 in
|
Compressive strength of cylinder (to nearest 10 psi)
|
6830 psi
|
Maximum load on cylinder 1
|
84070 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
0 hours
|
DIME Test ID: 2023-09-11-95-3
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/29/2023
Date Tested: 09/13/2023
Submitted By Organization: Myers and Sons Construction
Organization Address: 45 Morrison Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95838
Organization Email: vvincent@myers-sons.com
Organization Phone: (650) 864-2057
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
1
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C39 - Ground End
|
Average diameter of cylinder 1
|
8.00 in
|
Compressive strength of cylinder (to nearest 10 psi)
|
7290 psi
|
Maximum load on cylinder 1
|
90310 lb
|
Type of fracture pattern of cylinder 1
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
0 hours
|
DIME Test ID: 2023-09-11-95-4
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/29/2023
Date Tested: 09/14/2023
Submitted By Organization: Myers and Sons Construction
Organization Address: 45 Morrison Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95838
Organization Email: vvincent@myers-sons.com
Organization Phone: (650) 864-2057
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
1
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C39 - Ground End
|
Average diameter of cylinder 1
|
8.00 in
|
Compressive strength of cylinder (to nearest 10 psi)
|
7090 psi
|
Maximum load on cylinder 1
|
89140 lb
|
Type of fracture pattern of cylinder 1
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
0 hours
|
DIME Test ID: 2023-09-11-95-5
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/29/2023
Date Tested: 09/15/2023
Submitted By Organization: Myers and Sons Construction
Organization Address: 45 Morrison Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95838
Organization Email: vvincent@myers-sons.com
Organization Phone: (650) 864-2057
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
1
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C39 - Ground End
|
Average diameter of cylinder 1
|
8.00 in
|
Compressive strength of cylinder (to nearest 10 psi)
|
6890 psi
|
Maximum load on cylinder 1
|
85030 lb
|
Type of fracture pattern of cylinder 1
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
0 hours
|
DIME Test ID: 2023-09-11-95-6
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/29/2023
Date Tested: 09/16/2023
Submitted By Organization: Myers and Sons Construction
Organization Address: 45 Morrison Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95838
Organization Email: vvincent@myers-sons.com
Organization Phone: (650) 864-2057
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
1
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C39 - Ground End
|
Average diameter of cylinder 1
|
8.00 in
|
Compressive strength of cylinder (to nearest 10 psi)
|
7460 psi
|
Maximum load on cylinder 1
|
94760 lb
|
Type of fracture pattern of cylinder 1
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
0 hours
|
DIME Test ID: 2023-09-11-95-7
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/29/2023
Date Tested: 09/18/2023
Submitted By Organization: Myers and Sons Construction
Organization Address: 45 Morrison Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95838
Organization Email: vvincent@myers-sons.com
Organization Phone: (650) 864-2057
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
1
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C39 - Ground End
|
Average diameter of cylinder 1
|
8.00 in
|
Compressive strength of cylinder (to nearest 10 psi)
|
7460 psi
|
Maximum load on cylinder 1
|
94760 lb
|
Type of fracture pattern of cylinder 1
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
0 hours
|
DIME Test ID: 2023-09-11-95-8
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/29/2023
Date Tested: 09/26/2023
Submitted By Organization: Myers and Sons Construction
Organization Address: 45 Morrison Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95838
Organization Email: vvincent@myers-sons.com
Organization Phone: (650) 864-2057
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
1
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C39 - Ground End
|
Average diameter of cylinder 1
|
8.00 in
|
Compressive strength of cylinder (to nearest 10 psi)
|
6330 psi
|
Maximum load on cylinder 1
|
77580 lb
|
Type of fracture pattern of cylinder 1
|
5
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
0 hours
|
DIME Test ID: 2023-09-11-95-9
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/29/2023
Date Tested: 09/28/2023
Submitted By Organization: Myers and Sons Construction
Organization Address: 45 Morrison Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95838
Organization Email: vvincent@myers-sons.com
Organization Phone: (650) 864-2057
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
1
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C39 - Ground End
|
Average diameter of cylinder 1
|
8.00 in
|
Compressive strength of cylinder (to nearest 10 psi)
|
6600 psi
|
Maximum load on cylinder 1
|
82000 lb
|
Type of fracture pattern of cylinder 1
|
5
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
0 hours
|
DIME Test ID: 2023-09-11-95-10
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/29/2023
Date Tested: 10/03/2023
Submitted By Organization: Myers and Sons Construction
Organization Address: 45 Morrison Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95838
Organization Email: vvincent@myers-sons.com
Organization Phone: (650) 864-2057
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
1
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C39 - Ground End
|
Average diameter of cylinder 1
|
8.00 in
|
Compressive strength of cylinder (to nearest 10 psi)
|
6690 psi
|
Maximum load on cylinder 1
|
81140 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
0 hours
|
DIME Test ID: 2023-09-11-95-11
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/29/2023
Date Tested: 10/06/2023
Submitted By Organization: Myers and Sons Construction
Organization Address: 45 Morrison Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95838
Organization Email: vvincent@myers-sons.com
Organization Phone: (650) 864-2057
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
1
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C39 - Ground End
|
Average diameter of cylinder 1
|
8.00 in
|
Compressive strength of cylinder (to nearest 10 psi)
|
6680 psi
|
Maximum load on cylinder 1
|
82870 lb
|
Type of fracture pattern of cylinder 1
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
0 hours
|
DIME Test ID: 2023-09-11-95-12
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/29/2023
Date Tested: 10/10/2023
Submitted By Organization: Myers and Sons Construction
Organization Address: 45 Morrison Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95838
Organization Email: vvincent@myers-sons.com
Organization Phone: (650) 864-2057
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
1
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C39 - Ground End
|
Average diameter of cylinder 1
|
8.00 in
|
Compressive strength of cylinder (to nearest 10 psi)
|
7350 psi
|
Maximum load on cylinder 1
|
92440 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
0 hours
|
DIME Test ID: 2023-09-11-95-13
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/29/2023
Date Tested: 10/20/2023
Submitted By Organization: Myers and Sons Construction
Organization Address: 45 Morrison Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95838
Organization Email: vvincent@myers-sons.com
Organization Phone: (650) 864-2057
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
1
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C39 - Ground End
|
Average diameter of cylinder 1
|
8.00 in
|
Compressive strength of cylinder (to nearest 10 psi)
|
6350 psi
|
Maximum load on cylinder 1
|
80650 lb
|
Type of fracture pattern of cylinder 1
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
0 hours
|