Print Report | Back to Sample Detail

Sample Record for 2023-11-10-44

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 995107 DEA: 081P3104 EFIS: 0823000157 QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-60-21.369/21.369
Work Description:
Location Description:
Contractor Name: Ames Construction Inc.
Contractor Address: 2000 AMES DRIVE, BURNSVILLE, MN 55306
Resident Engineer: Matt Bruce Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2023-11-10-44
TL Number from the TL Form:
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 11/10/2023
Date that the sample was received by the laboratory/organization performing the testing: 11/15/2023
The quantity of what the sample constitutes: 4
A brief description of the sample: 4x8 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 1056-1110
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Robertson

Material Information

The concrete mix design number: SC675834
The truck number from where the sample was collected: Not Provided on TL
The batch plant ticket number from where the sample was collected: Not Provided on TL
Concrete batch plant: Robertson Banning
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Theodore St. OC Bridge Deck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 2

DIME Test ID: 2023-11-10-44-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Cured in accordance with ASTM C511
Verified Date: 11/17/2023
Date Tested: 11/17/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.63 in^2
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Compressive strength (to nearest 10 psi) 3580 psi
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.01 in
Compressive strength of cylinder 1 3667.5 psi
Compressive strength of cylinder 2 3489.3 psi
Maximum load on cylinder 1 46100 lb
Maximum load on cylinder 2 44070 lb
Type of fracture pattern of cylinder 1 2
Type of fracture pattern of cylinder 2 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 7 days

Test 2 of 2

DIME Test ID: 2023-11-10-44-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Cured in accordance with ASTM C511
Verified Date: 01/22/2024
Date Tested: 12/08/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 12.63 in^2
Cross sectional area of cylinder 2 12.63 in^2
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Compressive strength (to nearest 10 psi) 4770 psi
Average diameter of cylinder 1 4.01 in
Average diameter of cylinder 2 4.01 in
Compressive strength of cylinder 1 4935.9 psi
Compressive strength of cylinder 2 4612.8 psi
Maximum load on cylinder 1 62340 lb
Maximum load on cylinder 2 58260 lb
Type of fracture pattern of cylinder 1 2
Type of fracture pattern of cylinder 2 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 28 days