Project ID: 215425 DEA: 06360244 EFIS: 0613000005
QA Service Level: 1
DIST-CO-RTE-PM: 06-TUL-99-30.6/35.2
Work Description: Widen Freeway & Bridge Construction (Concrete Bridge)
Location Description:
Contractor Name: SECURITY PAVING COMPANY, INC.
Contractor Address: 13170 TELFAIR AVE, SYLMAR, CA, 91342
Resident Engineer: Javier Huerta Structure Rep.: Ramandeep Guraya
DIME Sample ID: 2023-08-17-82
TL Number from the TL Form:
Sample Submitted By Organization: CT D06 - Visalia Field Laboratory
Sample Organization Contact: (559) 341-4165
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 08/17/2023
Date that the sample was received by the laboratory/organization performing the testing: 08/18/2023
The quantity of what the sample constitutes: 9 CY
A brief description of the sample: Type II/IV Cement-4x8Concrete Cylinder
From where was the sample collected: Supplier
Laboratory sample identification:
Structure unique identifier:
Structure name: TUL 99- J St Bridge - Ave 264
The fabricator/manufacturer/facility name: CalPort Tul Plant
The concrete mix design number: 63241NOP
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: UnknownWheel
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Back of truck chute
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2023-08-17-82-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/14/2023
Date Tested: 09/27/2023
Submitted By Organization: CT D06 - Visalia Field Laboratory
Organization Address: 8530 West Roosevelt Avenue,
Organization City: Visalia
Organization State: CA
Organization Zipcode: 93291
Organization Email: shoaib.ahmed@dot.ca.gov
Organization Phone: (559) 341-4165
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
3
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
Average diameter of cylinder 1
|
4.00 in
|
Average diameter of cylinder 2
|
4.00 in
|
Average diameter of cylinder 3
|
4.00 in
|
Cross sectional area of cylinder 1
|
4 in^2
|
Cross sectional area of cylinder 2
|
4 in^2
|
Cross sectional area of cylinder 3
|
4 in^2
|
Compressive strength (to nearest 10 psi)
|
4220 psi
|
Maximum load on cylinder 1
|
51472 lb
|
Maximum load on cylinder 2
|
54426 lb
|
Maximum load on cylinder 3
|
53283 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Type of fracture pattern of cylinder 2
|
3
|
Type of fracture pattern of cylinder 3
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
A lot of fine material appeared after break.
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Correction factor for cylinder 3
|
1
|
Age of specimen
|
46 days
|
Age of specimen in hours
|
0 hours
|
DIME Test ID: 2023-08-17-82-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/14/2023
Date Tested: 09/27/2023
Submitted By Organization: CT D06 - Visalia Field Laboratory
Organization Address: 8530 West Roosevelt Avenue,
Organization City: Visalia
Organization State: CA
Organization Zipcode: 93291
Organization Email: shoaib.ahmed@dot.ca.gov
Organization Phone: (559) 341-4165
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
3
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
Average diameter of cylinder 1
|
4.00 in
|
Average diameter of cylinder 2
|
4.00 in
|
Average diameter of cylinder 3
|
4.00 in
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
Compressive strength (to nearest 10 psi)
|
3570 psi
|
Maximum load on cylinder 1
|
46016 lb
|
Maximum load on cylinder 2
|
45198 lb
|
Maximum load on cylinder 3
|
43252 lb
|
Type of fracture pattern of cylinder 1
|
3
|
Type of fracture pattern of cylinder 2
|
3
|
Type of fracture pattern of cylinder 3
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
Fines appeared upon break
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Correction factor for cylinder 3
|
1
|
Age of specimen
|
42 days
|
Age of specimen in hours
|
0 hours
|
DIME Test ID: 2023-08-17-82-3
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/14/2023
Date Tested: 09/21/2023
Submitted By Organization: CT D06 - Visalia Field Laboratory
Organization Address: 8530 West Roosevelt Avenue,
Organization City: Visalia
Organization State: CA
Organization Zipcode: 93291
Organization Email: shoaib.ahmed@dot.ca.gov
Organization Phone: (559) 341-4165
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
3
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
Average diameter of cylinder 1
|
4.00 in
|
Average diameter of cylinder 2
|
4.00 in
|
Average diameter of cylinder 3
|
4.00 in
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
Compressive strength (to nearest 10 psi)
|
4780 psi
|
Maximum load on cylinder 1
|
63302 lb
|
Maximum load on cylinder 2
|
58813 lb
|
Maximum load on cylinder 3
|
57959 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Type of fracture pattern of cylinder 2
|
2
|
Type of fracture pattern of cylinder 3
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Correction factor for cylinder 3
|
1
|
Age of specimen
|
42 days
|
Age of specimen in hours
|
0 hours
|
DIME Test ID: 2023-08-17-82-4
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/14/2023
Date Tested: 09/21/2023
Submitted By Organization: CT D06 - Visalia Field Laboratory
Organization Address: 8530 West Roosevelt Avenue,
Organization City: Visalia
Organization State: CA
Organization Zipcode: 93291
Organization Email: shoaib.ahmed@dot.ca.gov
Organization Phone: (559) 341-4165
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
3
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
Average diameter of cylinder 1
|
4.00 in
|
Average diameter of cylinder 2
|
4.00 in
|
Average diameter of cylinder 3
|
4.00 in
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
Compressive strength (to nearest 10 psi)
|
4480 psi
|
Maximum load on cylinder 1
|
57159 lb
|
Maximum load on cylinder 2
|
55401 lb
|
Maximum load on cylinder 3
|
56257 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Type of fracture pattern of cylinder 2
|
2
|
Type of fracture pattern of cylinder 3
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Correction factor for cylinder 3
|
1
|
Age of specimen
|
42 days
|
Age of specimen in hours
|
0 hours
|
DIME Test ID: 2023-08-17-82-5
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/14/2023
Date Tested: 09/19/2023
Submitted By Organization: CT D06 - Visalia Field Laboratory
Organization Address: 8530 West Roosevelt Avenue,
Organization City: Visalia
Organization State: CA
Organization Zipcode: 93291
Organization Email: shoaib.ahmed@dot.ca.gov
Organization Phone: (559) 341-4165
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
3
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
Average diameter of cylinder 1
|
4.00 in
|
Average diameter of cylinder 2
|
4.00 in
|
Average diameter of cylinder 3
|
4.00 in
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
Compressive strength (to nearest 10 psi)
|
4530 psi
|
Maximum load on cylinder 1
|
55055 lb
|
Maximum load on cylinder 2
|
58964 lb
|
Maximum load on cylinder 3
|
56941 lb
|
Type of fracture pattern of cylinder 1
|
3
|
Type of fracture pattern of cylinder 2
|
2
|
Type of fracture pattern of cylinder 3
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
With fines shown after break
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Correction factor for cylinder 3
|
1
|
Age of specimen
|
42 days
|
Age of specimen in hours
|
0 hours
|