Sample Record for 2023-10-25-31
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 994191 DEA: 081G8304 EFIS: 0816000079
QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-40-R100.8/R101.8
Work Description: HMA, STRUCTURAL CONC, BAR REINFORCING STEEL, CRSP & IMPORTED BORROW.
Location Description: SAN BERNARDINO COUNTY AT ESSEX FROM 1.1 MILES EAST OF ESSEX ROAD OVERCROSSING TO 0.5 MILE EAST OF HALFWAY HILLS WASH BRIDGE
Contractor Name: SKANSKA USA CIVIL WEST CALIFORNIA DISTRICT INC.
Contractor Address: 1995 Agua Mansa Rd, Riverside, CA 92509
Resident Engineer: Anthony Doan Structure Rep.: Jegbefume Adodo
Sample Information
DIME Sample ID: 2023-10-25-31
TL Number from the TL Form: 1053-5
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 10/25/2023
Date that the sample was received by the laboratory/organization performing the testing: 10/28/2023
The quantity of what the sample constitutes: 6
A brief description of the sample: Concrete Cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 1053-5
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Cemex
Material Information
The concrete mix design number: 1629101
The truck number from where the sample was collected: 10078318
The batch plant ticket number from where the sample was collected: 48028890
Concrete batch plant: Cemex
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Halfway Hills Wash Bridge EB - Abutment 1 Inner Piles
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
Test Results
Test 1 of 2
DIME Test ID: 2023-10-25-31-1
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 11/14/2023
Date Tested: 11/01/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
no data
|
|
Apparent mass of submerged cylinder 1
|
no data0 lb
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
3620 psi
|
|
Maximum load on cylinder 1
|
46440 lb
|
|
Maximum load on cylinder 2
|
43390 lb
|
|
Maximum load on cylinder 3
|
46580 lb
|
|
Compressive strength of cylinder 1
|
3690.0 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
3450.0 psi
|
|
Compressive strength of cylinder 3
|
3710 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Type of fracture pattern of cylinder 3
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
7 days
|
|
Age of specimen in hours
|
no data0 hours
|
|
Serial number of delivery ticket, if available
|
no data
|
Test 2 of 2
DIME Test ID: 2023-10-25-31-2
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 11/22/2023
Date Tested: 11/22/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
no data
|
|
Apparent mass of submerged cylinder 1
|
no data0 lb
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4910 psi
|
|
Maximum load on cylinder 1
|
60810 lb
|
|
Maximum load on cylinder 2
|
62080 lb
|
|
Maximum load on cylinder 3
|
62100 lb
|
|
Compressive strength of cylinder 1
|
4840.0 psi
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Compressive strength of cylinder 2
|
4940.0 psi
|
|
Compressive strength of cylinder 3
|
4940 psi
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Type of fracture pattern of cylinder 3
|
3
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
no data0 days
|
|
Age of specimen in hours
|
no data0 hours
|
|
Serial number of delivery ticket, if available
|
no data
|