Project ID: 214336 DEA: 07302404 EFIS: 0713000488
QA Service Level: 1
DIST-CO-RTE-PM: 07-VEN-101-37/40
Work Description: PADRE JUAN REHAB
Location Description: VEN 101
Contractor Name: GRANITE CONSTRUCTION COMPANY
Contractor Address: 4820 McGrath Street, Suite 101, Ventura, CA 93003
Resident Engineer: Alfred Ira Structure Rep.: Unknown
DIME Sample ID: 2023-10-14-15
TL Number from the TL Form:
Sample Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Sample Organization Contact: (213) 817-0387
Type of Sample: Department Acceptance
Type of Material: Concrete
Sample Taken Date: 10/14/2023
Date that the sample was received by the laboratory/organization performing the testing: 10/15/2023
The quantity of what the sample constitutes: 130 CY
A brief description of the sample: JPCP-RSC Beams
From where was the sample collected: Job Site
Laboratory sample identification: 23-1683
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Granite Rock
The concrete mix design number: G3-22-PRS-299
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: NA
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Batch Plant Loader Bucket
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2023-10-14-15-1
Test Method: CTM 524-March 2013: Method of Test for Flexural Strength Of Rapid Strength Concrete
Verified Date: 10/25/2023
Date Tested: 10/24/2023
Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Organization Address: 1940 South Workman Mill Road,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90601
Organization Email: chad.chotibhongs@dot.ca.gov
Organization Phone: (213) 817-0387
General Comments for this Test: VEN Rte. 101 R36.3/R40.6
North of Padre Juan Rd. OC
Sta. 2081+50 to Sta. 2089+14
Test Result Compliance:
Additional Comments When Verified:
Number of specimens
|
3
|
Does the testing machine measure load or stress on the beam specimen?
|
Stress
|
Fracture initiates in the tension surface
|
Within the Middle Third of the Span Length
|
Fracture occurred at a capped section
|
No
|
Is a beam dimensional correction factor used?
|
Yes
|
Age of specimen
|
10 days
|
Modulus of rupture
|
620 psi
|
Modulus of rupture average
|
690 psi
|
Modulus of rupture 2
|
750 psi
|
Modulus of rupture 3
|
700 psi
|