Sample Record for 2016-05-04-6
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 7613 DEA: 071218W4 EFIS: 0700021119
QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-5-29.4/31.6
Work Description: REALIGN ROUTE 5 AND RAILROAD TRACKS AND RECONFIGURE ON- AND OFF-RAMPS.
Location Description: LOS ANGELES COUNTY IN BURBANK FROM WEST MAGNOLIA BOULEVARD OVERCROSSING TO 0.3 MILE NORTH OF BUENA VISTA STREET/WINONA AVENUE UNDERCROSSING
Contractor Name: SECURITY PAVING COMPANY, INC.
Contractor Address: 13170 TELFAIR AVENUE, SYLMAR, CA 91342
Resident Engineer: Vladimir Gurfinkel Structure Rep.: Gon Choi
Sample Information
DIME Sample ID: 2016-05-04-6
TL Number from the TL Form: 178091
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 05/04/2016
Date that the sample was received by the laboratory/organization performing the testing: 05/06/2016
The quantity of what the sample constitutes: 6
A brief description of the sample: Concrete Cylinder 6 x 12
From where was the sample collected: Job Site
Laboratory sample identification: 889-91
Structure unique identifier: Unknown
Structure name: Unknown
The fabricator/manufacturer/facility name: National Ready Mix
Material Information
The concrete mix design number: S62578
The truck number from where the sample was collected: 439
The batch plant ticket number from where the sample was collected: 195668
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: Plant
A detailed description of where the material sample was collected: Chute
Where the material sample would have been placed if not sampled: Stem RW 1607
From Lot No.: Unknown
Bag Lot No.: Unknown
Test Results
Test 1 of 3
DIME Test ID: 2016-05-04-6-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 05/11/2016
Date Tested: 05/11/2016
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Average diameter of cylinder 1
|
5.98 in
|
Average diameter of cylinder 2
|
5.98 in
|
Cross sectional area of cylinder 1
|
28.09 in^2
|
Cross sectional area of cylinder 2
|
28.09 in^2
|
Compressive strength (to nearest 10 psi)
|
2210 psi
|
Maximum load on cylinder 1
|
61520 lb
|
Maximum load on cylinder 2
|
62510 lb
|
Compressive strength of cylinder 1
|
2190.1 psi
|
Type of fracture pattern of cylinder 1
|
3
|
Compressive strength of cylinder 2
|
2225.3 psi
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
no data
|
Age of specimen
|
7 days
|
Age of specimen in hours
|
no data
|
Test 2 of 3
DIME Test ID: 2016-05-04-6-2
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 05/18/2016
Date Tested: 05/18/2016
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Average diameter of cylinder 1
|
5.98 in
|
Average diameter of cylinder 2
|
5.98 in
|
Cross sectional area of cylinder 1
|
28.09 in^2
|
Cross sectional area of cylinder 2
|
28.09 in^2
|
Compressive strength (to nearest 10 psi)
|
2950 psi
|
Maximum load on cylinder 1
|
84250 lb
|
Maximum load on cylinder 2
|
81630 lb
|
Compressive strength of cylinder 1
|
2999.3 psi
|
Type of fracture pattern of cylinder 1
|
3
|
Compressive strength of cylinder 2
|
2906.0 psi
|
Type of fracture pattern of cylinder 2
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
no data
|
Age of specimen
|
14 days
|
Age of specimen in hours
|
no data
|
Test 3 of 3
DIME Test ID: 2016-05-04-6-3
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 06/01/2016
Date Tested: 06/01/2016
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Average diameter of cylinder 1
|
5.98 in
|
Average diameter of cylinder 2
|
5.98 in
|
Cross sectional area of cylinder 1
|
28.09 in^2
|
Cross sectional area of cylinder 2
|
28.09 in^2
|
Compressive strength (to nearest 10 psi)
|
4070 psi
|
Maximum load on cylinder 1
|
114670 lb
|
Maximum load on cylinder 2
|
114130 lb
|
Compressive strength of cylinder 1
|
4082.2 psi
|
Type of fracture pattern of cylinder 1
|
2
|
Compressive strength of cylinder 2
|
4063.0 psi
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
no data
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
no data
|