Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 994245 DEA: 051H4304 EFIS: 0516000073
QA Service Level: 1
DIST-CO-RTE-PM: 05-SB-101-21.4/21.9
Work Description: San Jose Creek Bridge replacement
Location Description: SANTA BARBARA COUNTY IN GOLETA FROM ROUTE 101/217 SEPARATION TO 0.3 MILE NORTH OF SAN JOSE CREEK BRIDGE
Contractor Name: MCM CONSTRUCTION
Contractor Address: 6413 32nd Street, North Highlands, Ca 95660
Resident Engineer: Manny Yogarajah Structure Rep.: Fabian Velasco
DIME Sample ID: 2023-10-05-24
TL Number from the TL Form:
Sample Submitted By Organization: Con-Fab California, LLC
Sample Organization Contact: (661) 630-7162
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 10/05/2023
Date that the sample was received by the laboratory/organization performing the testing: 10/06/2023
The quantity of what the sample constitutes: 28 CY
A brief description of the sample: T-II/V Cement & Flyash Type F
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier: 51-0367L/R
Structure name: San Jose Creek Bridge
The fabricator/manufacturer/facility name: Con-Fab California, LLC - Shafter
The concrete mix design number: S9.8-25FA
The truck number from where the sample was collected: 113
The batch plant ticket number from where the sample was collected: 3802
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Sampled from wheelbarrow collected from chute of ready mix truck
Where the material sample would have been placed if not sampled: Box Girder
From Lot No.:
Bag Lot No.:
DIME Test ID: 2023-10-05-24-1
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 06/11/2024
Date Tested: 10/05/2023
Submitted By Organization: Con-Fab California, LLC
Organization Address: 701 Golds Avenue,
Organization City: Shafter
Organization State: CA
Organization Zipcode: 93263
Organization Email: benjamina@confabca.com
Organization Phone: (661) 630-3283
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
DIME Test ID: 2023-10-05-24-2
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 06/11/2024
Date Tested: 10/05/2023
Submitted By Organization: Con-Fab California, LLC
Organization Address: 701 Golds Avenue,
Organization City: Shafter
Organization State: CA
Organization Zipcode: 93263
Organization Email: benjamina@confabca.com
Organization Phone: (661) 630-3283
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
DIME Test ID: 2023-10-05-24-3
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 06/11/2024
Date Tested: 10/06/2023
Submitted By Organization: Con-Fab California, LLC
Organization Address: 701 Golds Avenue,
Organization City: Shafter
Organization State: CA
Organization Zipcode: 93263
Organization Email: benjamina@confabca.com
Organization Phone: (661) 630-3283
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
6
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
no data
|
|
Apparent mass of submerged cylinder 1
|
1 lb
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Average diameter of cylinder 4
|
4.00 in
|
|
Average diameter of cylinder 5
|
4.00 in
|
|
Average diameter of cylinder 6
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.56 in^2
|
|
Cross sectional area of cylinder 2
|
12.56 in^2
|
|
Cross sectional area of cylinder 3
|
12.56 in^2
|
|
Cross sectional area of cylinder 4
|
12.56 in^2
|
|
Cross sectional area of cylinder 5
|
12.56 in^2
|
|
Cross sectional area of cylinder 6
|
12.56 in^2
|
|
Compressive strength (to nearest 10 psi)
|
5000 psi
|
|
Maximum load on cylinder 1
|
60690 lb
|
|
Maximum load on cylinder 2
|
60745 lb
|
|
Maximum load on cylinder 3
|
60120 lb
|
|
Maximum load on cylinder 4
|
63300 lb
|
|
Maximum load on cylinder 5
|
65570 lb
|
|
Maximum load on cylinder 6
|
67245 lb
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Type of fracture pattern of cylinder 3
|
3
|
|
Type of fracture pattern of cylinder 4
|
2
|
|
Type of fracture pattern of cylinder 5
|
3
|
|
Type of fracture pattern of cylinder 6
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Correction factor for cylinder 4
|
1
|
|
Correction factor for cylinder 5
|
1
|
|
Correction factor for cylinder 6
|
1
|
|
Age of specimen
|
no data0 days
|
|
Age of specimen in hours
|
16 hours
|
|
Serial number of delivery ticket, if available
|
no data
|
DIME Test ID: 2023-10-05-24-4
Test Method: CTM TEMP1-16: Test Method for Monitoring Precast Concrete Curing Temperature (Curing temperature)
Verified Date: 06/11/2024
Date Tested: 10/05/2023
Submitted By Organization: Con-Fab California, LLC
Organization Address: 701 Golds Avenue,
Organization City: Shafter
Organization State: CA
Organization Zipcode: 93263
Organization Email: benjamina@confabca.com
Organization Phone: (661) 630-3283
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Precast Maximum Curing Temperature
|
147 °F
|
DIME Test ID: 2023-10-05-24-5
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 06/11/2024
Date Tested: 11/02/2023
Submitted By Organization: Con-Fab California, LLC
Organization Address: 701 Golds Avenue,
Organization City: Shafter
Organization State: CA
Organization Zipcode: 93263
Organization Email: benjamina@confabca.com
Organization Phone: (661) 630-3283
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
no data
|
|
Apparent mass of submerged cylinder 1
|
1 lb
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.56 in^2
|
|
Cross sectional area of cylinder 2
|
12.56 in^2
|
|
Cross sectional area of cylinder 3
|
12.56 in^2
|
|
Compressive strength (to nearest 10 psi)
|
9260 psi
|
|
Maximum load on cylinder 1
|
113445 lb
|
|
Maximum load on cylinder 2
|
118665 lb
|
|
Maximum load on cylinder 3
|
116985 lb
|
|
Type of fracture pattern of cylinder 1
|
4
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Type of fracture pattern of cylinder 3
|
3
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
28 days
|
|
Age of specimen in hours
|
no data0 hours
|
|
Serial number of delivery ticket, if available
|
no data
|
DIME Test ID: 2023-10-05-24-6
Test Method: ASTM C138-17a: Standard Test Method for Density (Unit Weight), Yield, and Air Content (Gravimetric) of Concrete
Verified Date: 06/11/2024
Date Tested: 10/05/2023
Submitted By Organization: Con-Fab California, LLC
Organization Address: 701 Golds Avenue,
Organization City: Shafter
Organization State: CA
Organization Zipcode: 93263
Organization Email: benjamina@confabca.com
Organization Phone: (661) 630-3283
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Identification of concrete represented by the sample
|
I Girders
|
|
Volume of the measure
|
0.25 ft^3
|
|
Density of concrete
|
151.4 lb/ft^3
|
|
Yield of concrete
|
no data
|
|
Relative yield of the batch
|
no data
|
|
Cement content
|
no data
|
|
Air content
|
no data
|
DIME Test ID: 2023-10-05-24-7
Test Method: ASTM C231-17a: Standard Test Method for Air Content of Freshly Mixed Concrete by the Pressure Method
Verified Date: 06/11/2024
Date Tested: 10/05/2023
Submitted By Organization: Con-Fab California, LLC
Organization Address: 701 Golds Avenue,
Organization City: Shafter
Organization State: CA
Organization Zipcode: 93263
Organization Email: benjamina@confabca.com
Organization Phone: (661) 630-3283
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified: