Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 215753 DEA: 050N72U4 EFIS: 0520000169
QA Service Level: 1
DIST-CO-RTE-PM: 05-SB-101-4.4/R7.7
Work Description: Please cc Office Engineer Ni Nyoman Paul on reports sent to RE and SR. Construct High Occupancy Vehicle (HOV) lanes on U.S. Route 101 and rehabilitation - Segment 4B.
Location Description: 101 freeway in Summerland, CA
Contractor Name: GRANITE CONSTRUCTION COMPANY
Contractor Address: 5335 Debbie Road, Santa Barbara, CA 93111
Resident Engineer: Luobao Cai Structure Rep.: Emiliano Berntsen
DIME Sample ID: 2023-08-14-30
TL Number from the TL Form:
Sample Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Sample Organization Contact: (805) 621-3616
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 08/14/2023
Date that the sample was received by the laboratory/organization performing the testing: 08/14/2023
The quantity of what the sample constitutes: 237.5 CY
A brief description of the sample: PCC
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Calportland Lompoc
The concrete mix design number: 710RH1010S
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 1890230
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Back of truck discharge chute in wheelbarrow
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2023-08-14-30-1
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 08/16/2023
Date Tested: 08/14/2023
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
DIME Test ID: 2023-08-14-30-2
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 08/16/2023
Date Tested: 08/14/2023
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
DIME Test ID: 2023-08-14-30-3
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 08/25/2023
Date Tested: 08/22/2023
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
3
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
no data
|
Apparent mass of submerged cylinder 1
|
no data0 lb
|
Average diameter of cylinder 1
|
4.01 in
|
Average diameter of cylinder 2
|
4.01 in
|
Average diameter of cylinder 3
|
4.01 in
|
Cross sectional area of cylinder 1
|
12.63 in^2
|
Cross sectional area of cylinder 2
|
12.63 in^2
|
Cross sectional area of cylinder 3
|
12.63 in^2
|
Compressive strength (to nearest 10 psi)
|
6670 psi
|
Maximum load on cylinder 1
|
82510 lb
|
Maximum load on cylinder 2
|
87310 lb
|
Maximum load on cylinder 3
|
82830 lb
|
Compressive strength of cylinder 1
|
6530.0 psi
|
Type of fracture pattern of cylinder 1
|
3
|
Compressive strength of cylinder 2
|
6910.0 psi
|
Compressive strength of cylinder 3
|
6560 psi
|
Type of fracture pattern of cylinder 2
|
5
|
Type of fracture pattern of cylinder 3
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Correction factor for cylinder 3
|
1
|
Age of specimen
|
8 days
|
Age of specimen in hours
|
no data0 hours
|
Serial number of delivery ticket, if available
|
no data
|
DIME Test ID: 2023-08-14-30-4
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 09/11/2023
Date Tested: 09/11/2023
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
3
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
no data
|
Apparent mass of submerged cylinder 1
|
no data0 lb
|
Average diameter of cylinder 1
|
4.02 in
|
Average diameter of cylinder 2
|
4.01 in
|
Average diameter of cylinder 3
|
4.01 in
|
Cross sectional area of cylinder 1
|
12.69 in^2
|
Cross sectional area of cylinder 2
|
12.63 in^2
|
Cross sectional area of cylinder 3
|
12.63 in^2
|
Compressive strength (to nearest 10 psi)
|
8960 psi
|
Maximum load on cylinder 1
|
116410 lb
|
Maximum load on cylinder 2
|
107780 lb
|
Maximum load on cylinder 3
|
116020 lb
|
Compressive strength of cylinder 1
|
9170.0 psi
|
Type of fracture pattern of cylinder 1
|
3
|
Compressive strength of cylinder 2
|
8530.0 psi
|
Compressive strength of cylinder 3
|
9190 psi
|
Type of fracture pattern of cylinder 2
|
2
|
Type of fracture pattern of cylinder 3
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Correction factor for cylinder 3
|
1
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
no data0 hours
|
Serial number of delivery ticket, if available
|
no data
|
DIME Test ID: 2023-08-14-30-5
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
Data has not been verified.