REPORT OF LABORATORY TESTING |
||||
Resident Engineer: |
Richard Duncan |
Date Reported: |
02/24/2016 |
|
Address: |
TL Number: |
161401 |
||
City: |
||||
Project Name: CONSTRUCT PETALUMA BLVD SOUTH INTERCHANGE, REPLACE PETALUMA RIVER BR |
||||
Prime Contractor: GHILOTTI - CC MYERS JV |
||||
Sample Taken Date: |
01/27/2016 |
Mix Design: |
4700 |
|
Contractor: Unknown |
Location : SONOMA COUNTY IN AND NEAR PETALUMA FROM GUNN DRIVE TO ROUTE 101/116 SEPARATION AND OVERHEAD |
|||
Structure unique identifier: Unknown |
||||
Structure name: Unknown |
||||
Location of Pour: soldier pile wall |
The following testing has been tested in accordance with:
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Cured in accordance with ASTM C511
Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 5.97 | 27.99 | 190625 | 6810.5 | 1 |
2 | 5.94 | 27.71 | 188420 | 6799.7 | 1 |
DIME Test ID: 2016-01-27-4-1
Number of specimens: 2
Compressive strength (to nearest 10 psi): 6810
Age of specimen: 28 days