Project ID: 994408 DEA: 051K03U4 EFIS: 0522000026
QA Service Level: 1
DIST-CO-RTE-PM: 05-SLO-101-
Work Description: !!PLEASE CC Office Engineer Barbara Riccardi on reports to RE and SR!! Construct 2 roundabouts in Montecito along US 101.
Location Description:
Contractor Name: Veronica Mchugh
Contractor Address: 5335 DEBBIE ROAD, SANTA BARBARA, CA 93111
Resident Engineer: Taylor Merlo Structure Rep.: Josh Madrigal
DIME Sample ID: 2023-05-26-54
TL Number from the TL Form:
Sample Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Sample Organization Contact: (805) 621-3616
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 05/26/2023
Date that the sample was received by the laboratory/organization performing the testing: 05/26/2023
The quantity of what the sample constitutes: 36 CY
A brief description of the sample: PCC
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name: RW 130 Stem
The fabricator/manufacturer/facility name: Martin Marietta
The concrete mix design number: 1614705
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 30758836
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Discharge from concrete truck into wheelbarrow
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2023-05-26-54-1
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 07/13/2023
Date Tested: 05/30/2023
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: does not comply
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
no data
|
|
Apparent mass of submerged cylinder 1
|
no data0 lb
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.01 in
|
|
Average diameter of cylinder 3
|
4.01 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.63 in^2
|
|
Cross sectional area of cylinder 3
|
12.63 in^2
|
|
Compressive strength (to nearest 10 psi)
|
3160 psi
|
|
Maximum load on cylinder 1
|
40560 lb
|
|
Maximum load on cylinder 2
|
41560 lb
|
|
Maximum load on cylinder 3
|
37540 lb
|
|
Compressive strength of cylinder 1
|
3230.0 psi
|
|
Type of fracture pattern of cylinder 1
|
5
|
|
Compressive strength of cylinder 2
|
3290.0 psi
|
|
Compressive strength of cylinder 3
|
2970 psi
|
|
Type of fracture pattern of cylinder 2
|
5
|
|
Type of fracture pattern of cylinder 3
|
5
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
4 days
|
|
Age of specimen in hours
|
no data0 hours
|
|
Serial number of delivery ticket, if available
|
no data
|
DIME Test ID: 2023-05-26-54-2
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 07/13/2023
Date Tested: 06/23/2023
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
no data
|
|
Apparent mass of submerged cylinder 1
|
no data0 lb
|
|
Average diameter of cylinder 1
|
4.01 in
|
|
Average diameter of cylinder 2
|
4.01 in
|
|
Average diameter of cylinder 3
|
4.01 in
|
|
Cross sectional area of cylinder 1
|
12.63 in^2
|
|
Cross sectional area of cylinder 2
|
12.63 in^2
|
|
Cross sectional area of cylinder 3
|
12.63 in^2
|
|
Compressive strength (to nearest 10 psi)
|
6770 psi
|
|
Maximum load on cylinder 1
|
89960 lb
|
|
Maximum load on cylinder 2
|
85080 lb
|
|
Maximum load on cylinder 3
|
81560 lb
|
|
Compressive strength of cylinder 1
|
7120.0 psi
|
|
Type of fracture pattern of cylinder 1
|
5
|
|
Compressive strength of cylinder 2
|
6740.0 psi
|
|
Compressive strength of cylinder 3
|
6460 psi
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Type of fracture pattern of cylinder 3
|
5
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
28 days
|
|
Age of specimen in hours
|
no data0 hours
|
|
Serial number of delivery ticket, if available
|
no data
|
DIME Test ID: 2023-05-26-54-3
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 07/13/2023
Date Tested: 07/07/2023
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
no data
|
|
Apparent mass of submerged cylinder 1
|
no data0 lb
|
|
Average diameter of cylinder 1
|
4.01 in
|
|
Average diameter of cylinder 2
|
4.01 in
|
|
Average diameter of cylinder 3
|
4.01 in
|
|
Cross sectional area of cylinder 1
|
12.63 in^2
|
|
Cross sectional area of cylinder 2
|
12.63 in^2
|
|
Cross sectional area of cylinder 3
|
12.63 in^2
|
|
Compressive strength (to nearest 10 psi)
|
7010 psi
|
|
Maximum load on cylinder 1
|
87140 lb
|
|
Maximum load on cylinder 2
|
88590 lb
|
|
Maximum load on cylinder 3
|
90040 lb
|
|
Compressive strength of cylinder 1
|
6900.0 psi
|
|
Type of fracture pattern of cylinder 1
|
5
|
|
Compressive strength of cylinder 2
|
7010.0 psi
|
|
Compressive strength of cylinder 3
|
7130 psi
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Type of fracture pattern of cylinder 3
|
3
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
42 days
|
|
Age of specimen in hours
|
no data0 hours
|
|
Serial number of delivery ticket, if available
|
no data
|