Project ID: 212112 DEA: 080C2514 EFIS: 0816000076 COOP: 081645
QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-10-0.0/13.2
Work Description: Design-Build of I-10 Corridor Contract 1 - Adding 2 new Express Lanes
Location Description: LA/SBD County Line to PM 13.2 near I-15
Contractor Name: Lane-Security Paving Joint Venture
Contractor Address: 3450 Centre Lake Drive, 1st Floor, Ontario, CA 91761
Resident Engineer: Jose Corona Structure Rep.: Luis Negrete
DIME Sample ID: 2023-07-12-9
TL Number from the TL Form: 712A
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 07/12/2023
Date that the sample was received by the laboratory/organization performing the testing: 07/13/2023
The quantity of what the sample constitutes: 6
A brief description of the sample: 6x12
From where was the sample collected: Job Site
Laboratory sample identification: 1015-712A
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Lane Security Paving Joint Venture
The concrete mix design number: 1610974
The truck number from where the sample was collected: NA
The batch plant ticket number from where the sample was collected: NA
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: RTE 10 4th St. Stage 5 Abut Footing
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2023-07-12-9-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C1231 - Unbonded Elastomeric Pad Cap Cured in accordance with ASTM C511
Verified Date: 08/07/2023
Date Tested: 07/19/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Cross sectional area of cylinder 1
|
27.99 in^2
|
|
Cross sectional area of cylinder 2
|
28.09 in^2
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Compressive strength (to nearest 10 psi)
|
4410 psi
|
|
Average diameter of cylinder 1
|
5.97 in
|
|
Average diameter of cylinder 2
|
5.98 in
|
|
Compressive strength of cylinder 1
|
4477.0 psi
|
|
Compressive strength of cylinder 2
|
4335.5 psi
|
|
Maximum load on cylinder 1
|
125310 lb
|
|
Maximum load on cylinder 2
|
121785 lb
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Age of specimen
|
7 days
|
DIME Test ID: 2023-07-12-9-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C1231 - Unbonded Elastomeric Pad Cap Cured in accordance with ASTM C511
Verified Date: 08/07/2023
Date Tested: 07/26/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Cross sectional area of cylinder 1
|
28.09 in^2
|
|
Cross sectional area of cylinder 2
|
27.99 in^2
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Compressive strength (to nearest 10 psi)
|
4830 psi
|
|
Average diameter of cylinder 1
|
5.98 in
|
|
Average diameter of cylinder 2
|
5.97 in
|
|
Compressive strength of cylinder 1
|
4861.7 psi
|
|
Compressive strength of cylinder 2
|
4792.2 psi
|
|
Maximum load on cylinder 1
|
136565 lb
|
|
Maximum load on cylinder 2
|
134135 lb
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Age of specimen
|
14 days
|
DIME Test ID: 2023-07-12-9-3
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap Cured in accordance with ASTM C511
Verified Date: 08/15/2023
Date Tested: 08/09/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Cross sectional area of cylinder 1
|
28.18 in^2
|
|
Cross sectional area of cylinder 2
|
28.18 in^2
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Compressive strength (to nearest 10 psi)
|
5240 psi
|
|
Average diameter of cylinder 1
|
5.99 in
|
|
Average diameter of cylinder 2
|
5.99 in
|
|
Compressive strength of cylinder 1
|
5211.1 psi
|
|
Compressive strength of cylinder 2
|
5259.0 psi
|
|
Maximum load on cylinder 1
|
146850 lb
|
|
Maximum load on cylinder 2
|
148200 lb
|
|
Type of fracture pattern of cylinder 1
|
1
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Age of specimen
|
28 days
|