Sample Record for 2023-06-14-69
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 214337 DEA: 080E33U4 EFIS: 0817000075
QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-115-R7.3/R10.0
Work Description: ADD WB AUX & EB DECEL LANES, WIDEN I15 SW CONNECT,RAMPS/BRDG
Location Description: SAN BERNARDINO COUNTY IN ONTARIO FROM 0.2 MILE WEST OF CUCAMONGA CREEK BRIDGE TO MILLIKEN AVENUE
Contractor Name: Ames Construction
Contractor Address: 391 North Main Street, Suite 302, Corona, CA 92880
Resident Engineer: Denise Sostrom Structure Rep.: Matt Bruce
Sample Information
DIME Sample ID: 2023-06-14-69
TL Number from the TL Form: 1040-614A
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 06/14/2023
Date that the sample was received by the laboratory/organization performing the testing: 05/27/2022
The quantity of what the sample constitutes: 6 cylinder
A brief description of the sample: 4x8 cylinder
From where was the sample collected: Job Site
Laboratory sample identification: 1040-614A
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Boral
Material Information
The concrete mix design number: SM445B37
The truck number from where the sample was collected: 1712
The batch plant ticket number from where the sample was collected: 7850790
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: PIER 2 AND 3 FOOTINGS
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
Test Results
Test 1 of 3
DIME Test ID: 2023-06-14-69-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Verified Date: 06/26/2023
Date Tested: 06/21/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
12.63 in^2
|
Cross sectional area of cylinder 2
|
12.63 in^2
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
Compressive strength (to nearest 10 psi)
|
4140 psi
|
Average diameter of cylinder 1
|
4.01 in
|
Average diameter of cylinder 2
|
4.01 in
|
Compressive strength of cylinder 1
|
4095.0 psi
|
Compressive strength of cylinder 2
|
4187.6 psi
|
Maximum load on cylinder 1
|
51720 lb
|
Maximum load on cylinder 2
|
52890 lb
|
Type of fracture pattern of cylinder 1
|
1
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
7 days
|
Test 2 of 3
DIME Test ID: 2023-06-14-69-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Verified Date: 06/28/2023
Date Tested: 06/28/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
12.69 in^2
|
Cross sectional area of cylinder 2
|
12.63 in^2
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
Compressive strength (to nearest 10 psi)
|
4860 psi
|
Average diameter of cylinder 1
|
4.02 in
|
Average diameter of cylinder 2
|
4.01 in
|
Compressive strength of cylinder 1
|
4754.1 psi
|
Compressive strength of cylinder 2
|
4973.1 psi
|
Maximum load on cylinder 1
|
60330 lb
|
Maximum load on cylinder 2
|
62810 lb
|
Type of fracture pattern of cylinder 1
|
3
|
Type of fracture pattern of cylinder 2
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
14 days
|
Test 3 of 3
DIME Test ID: 2023-06-14-69-3
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C1231 - Unbonded Elastomeric Pad Cap
Verified Date: 07/13/2023
Date Tested: 07/12/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
12.63 in^2
|
Cross sectional area of cylinder 2
|
12.63 in^2
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
Compressive strength (to nearest 10 psi)
|
5740 psi
|
Average diameter of cylinder 1
|
4.01 in
|
Average diameter of cylinder 2
|
4.01 in
|
Compressive strength of cylinder 1
|
6003.2 psi
|
Compressive strength of cylinder 2
|
5472.7 psi
|
Maximum load on cylinder 1
|
75820 lb
|
Maximum load on cylinder 2
|
69120 lb
|
Type of fracture pattern of cylinder 1
|
1
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
28 days
|