Sample Record for 2023-05-22-84

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 994296 DEA: 07336004 EFIS: 0716000375 QA Service Level: 1
DIST-CO-RTE-PM: 07-VEN-118-R1.4/1.8
Work Description: CONSTRUCT STORMWATER TREATMENT DEVICES.
Location Description: IN VENTURA COUNTY NEAR SATICOY FROM 0.2 MILE EAST OF NARDO STREET TO 0.1 MILE WEST OF SANTA CLARA RIVER
Contractor Name: BEADOR CONSTRUCTION
Contractor Address: 2900 Bristol Street, Suite D204, Costa Mesa, CA 92626
Resident Engineer: DENRICK BAUTISTA Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2023-05-22-84
TL Number from the TL Form: 146777
Sample Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Sample Organization Contact: (213) 817-0387
Type of Sample: Department Acceptance
Type of Material: Concrete
Sample Taken Date: 05/22/2023
Date that the sample was received by the laboratory/organization performing the testing: 05/23/2023
The quantity of what the sample constitutes: 130 CY
A brief description of the sample: 4X8 PCC cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 23-146
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Beador Construction

Material Information

The concrete mix design number: SL675330
The truck number from where the sample was collected: NA
The batch plant ticket number from where the sample was collected: NA
Concrete batch plant: NA
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: truck chute
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 2

DIME Test ID: 2023-05-22-84-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 06/19/2023
Date Tested: 06/19/2023
Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Organization Address: 1940 South Workman Mill Road,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90601
Organization Email: chad.chotibhongs@dot.ca.gov
Organization Phone: (213) 407-6963
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 4.03 in
Average diameter of cylinder 2 4.02 in
Average diameter of cylinder 3 4.01 in
Cross sectional area of cylinder 1 12.76 in^2
Cross sectional area of cylinder 2 12.69 in^2
Cross sectional area of cylinder 3 12.63 in^2
Compressive strength (to nearest 10 psi) 6630 psi
Maximum load on cylinder 1 84792 lb
Maximum load on cylinder 2 83756 lb
Maximum load on cylinder 3 83892 lb
Compressive strength of cylinder 1 6645.1 psi
Type of fracture pattern of cylinder 1 2
Compressive strength of cylinder 2 6600.2 psi
Compressive strength of cylinder 3 6642.3 psi
Type of fracture pattern of cylinder 2 2
Type of fracture pattern of cylinder 3 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 28 days
Age of specimen in hours no data0 hours

Test 2 of 2

DIME Test ID: 2023-05-22-84-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 07/03/2023
Date Tested: 07/03/2023
Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Organization Address: 1940 South Workman Mill Road,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90601
Organization Email: chad.chotibhongs@dot.ca.gov
Organization Phone: (213) 407-6963
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 4.01 in
Average diameter of cylinder 2 4.03 in
Average diameter of cylinder 3 4.03 in
Cross sectional area of cylinder 1 12.63 in^2
Cross sectional area of cylinder 2 12.76 in^2
Cross sectional area of cylinder 3 12.76 in^2
Compressive strength (to nearest 10 psi) 6660 psi
Maximum load on cylinder 1 84212 lb
Maximum load on cylinder 2 85008 lb
Maximum load on cylinder 3 84926 lb
Compressive strength of cylinder 1 6667.6 psi
Type of fracture pattern of cylinder 1 2
Compressive strength of cylinder 2 6662.1 psi
Compressive strength of cylinder 3 6655.6 psi
Type of fracture pattern of cylinder 2 2
Type of fracture pattern of cylinder 3 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 42 days
Age of specimen in hours no data0 hours