Project ID: 213741 DEA: 07325704 EFIS: 0716000089
QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-5-1.7
Work Description: BUILDING CONSTRUCTION IN LOS ANGELES COUNTY IN SANTA FE SPRINGS AT 14044 FREEWAY DRIVE.
Location Description: Santa Fe Springs, At 14044 Freeway Drive.
Contractor Name: AWI Builders Inc
Contractor Address: 7831 Paramount Bl, Pico Rivera Ca 90660
Resident Engineer: Mashhur Ali Structure Rep.: Nelson Parada
DIME Sample ID: 2023-06-13-53
TL Number from the TL Form: NA
Sample Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Sample Organization Contact: (213) 817-0387
Type of Sample: Department Acceptance
Type of Material: Concrete
Sample Taken Date: 06/13/2023
Date that the sample was received by the laboratory/organization performing the testing: 06/14/2023
The quantity of what the sample constitutes: 130 CY
A brief description of the sample: 6X12 PCC cylinder
From where was the sample collected: Job Site
Laboratory sample identification: 23-189
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Robertsons Ready Mix
The concrete mix design number: SC590B33
The truck number from where the sample was collected: 1
The batch plant ticket number from where the sample was collected: NA
Concrete batch plant: Robertsons Ready Mix
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: truck chute
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2023-06-13-53-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 06/19/2023
Date Tested: 06/18/2023
Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Organization Address: 1940 South Workman Mill Road,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90601
Organization Email: chad.chotibhongs@dot.ca.gov
Organization Phone: (213) 407-6963
General Comments for this Test:
Test Result Compliance: not applicable
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
5.98 in
|
|
Average diameter of cylinder 2
|
6.01 in
|
|
Cross sectional area of cylinder 1
|
28.09 in^2
|
|
Cross sectional area of cylinder 2
|
28.37 in^2
|
|
Compressive strength (to nearest 10 psi)
|
3470 psi
|
|
Maximum load on cylinder 1
|
95679 lb
|
|
Maximum load on cylinder 2
|
100095 lb
|
|
Compressive strength of cylinder 1
|
3406.2 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
3528.2 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Age of specimen
|
5 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2023-06-13-53-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 06/20/2023
Date Tested: 06/20/2023
Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Organization Address: 1940 South Workman Mill Road,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90601
Organization Email: chad.chotibhongs@dot.ca.gov
Organization Phone: (213) 407-6963
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
5.98 in
|
|
Average diameter of cylinder 2
|
6.02 in
|
|
Cross sectional area of cylinder 1
|
28.09 in^2
|
|
Cross sectional area of cylinder 2
|
28.46 in^2
|
|
Compressive strength (to nearest 10 psi)
|
3950 psi
|
|
Maximum load on cylinder 1
|
110926 lb
|
|
Maximum load on cylinder 2
|
112635 lb
|
|
Compressive strength of cylinder 1
|
3948.9 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
3957.7 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Age of specimen
|
7 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2023-06-13-53-3
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 07/05/2023
Date Tested: 07/04/2023
Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Organization Address: 1940 South Workman Mill Road,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90601
Organization Email: chad.chotibhongs@dot.ca.gov
Organization Phone: (213) 407-6963
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
6.03 in
|
|
Average diameter of cylinder 2
|
6.03 in
|
|
Cross sectional area of cylinder 1
|
28.56 in^2
|
|
Cross sectional area of cylinder 2
|
28.56 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4890 psi
|
|
Maximum load on cylinder 1
|
139280 lb
|
|
Maximum load on cylinder 2
|
139872 lb
|
|
Compressive strength of cylinder 1
|
4876.8 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
4897.5 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Age of specimen
|
21 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2023-06-13-53-4
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 07/11/2023
Date Tested: 07/11/2023
Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Organization Address: 1940 South Workman Mill Road,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90601
Organization Email: chad.chotibhongs@dot.ca.gov
Organization Phone: (213) 407-6963
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
5.99 in
|
|
Average diameter of cylinder 2
|
6.02 in
|
|
Cross sectional area of cylinder 1
|
28.18 in^2
|
|
Cross sectional area of cylinder 2
|
28.46 in^2
|
|
Compressive strength (to nearest 10 psi)
|
5140 psi
|
|
Maximum load on cylinder 1
|
145514 lb
|
|
Maximum load on cylinder 2
|
145892 lb
|
|
Compressive strength of cylinder 1
|
5163.7 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
5126.2 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Age of specimen
|
28 days
|
|
Age of specimen in hours
|
no data0 hours
|