QA Service Level: 1
DIST-CO-RTE-PM: 06-FRE-41-R27.4/R28.5
Work Description: REMOVE AC PAVEMENT, WIDEN TRAVEL WAY, AND CONSTRUCT RETAINING WALL.
Location Description: FRESNO COUNTY IN FRESNO FROM 0.1 MILE SOUTH OF ASHLAN AVENUE OVERCROSSING TO SHAW AVENUE OVERCROSSING
Contractor Name: RNR Construction, Inc
Contractor Address: 8589 Thys Court, Sacramento, CA,95828
Resident Engineer: Mark Mengoni Structure Rep.: Benjamin Holton
DIME Sample ID: 2023-05-05-51
TL Number from the TL Form:
Sample Submitted By Organization: CT D06 - Millbrook Field Laboratory
Sample Organization Contact: (559) 341-3953
Type of Sample: Department Acceptance
Type of Material: Concrete
Sample Taken Date: 05/05/2023
Date that the sample was received by the laboratory/organization performing the testing: 05/06/2023
The quantity of what the sample constitutes: 300 cy
A brief description of the sample: structural concrete
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name: CIDH Foundation
The fabricator/manufacturer/facility name: Unknown
The concrete mix design number: 1549279
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: Unknown
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Discharge from concrete truck into wheelbarrow.
Where the material sample would have been placed if not sampled: CIDH Foundation
From Lot No.:
Bag Lot No.:
DIME Test ID: 2023-05-05-51-1
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 05/15/2023
Date Tested: 05/12/2023
Submitted By Organization: CT D06 - Millbrook Field Laboratory
Organization Address: 1352 W. Olive Ave,
Organization City: Fresno
Organization State: CA
Organization Zipcode: 93728
Organization Email: tomas.silva@dot.ca.gov
Organization Phone: (559) 417-5341
General Comments for this Test:
Test Result Compliance: does not comply
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
3170 psi
|
|
Maximum load on cylinder 1
|
36420 lb
|
|
Maximum load on cylinder 2
|
33640 lb
|
|
Maximum load on cylinder 3
|
49470 lb
|
|
Compressive strength of cylinder 1
|
2897.4 psi
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Compressive strength of cylinder 2
|
2676.2 psi
|
|
Compressive strength of cylinder 3
|
3935.6 psi
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Type of fracture pattern of cylinder 3
|
3
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
7 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2023-05-05-51-2
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 06/02/2023
Date Tested: 06/02/2023
Submitted By Organization: CT D06 - Millbrook Field Laboratory
Organization Address: 1352 W. Olive Ave,
Organization City: Fresno
Organization State: CA
Organization Zipcode: 93728
Organization Email: tomas.silva@dot.ca.gov
Organization Phone: (559) 417-5341
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Average diameter of cylinder 1
|
4.01 in
|
|
Average diameter of cylinder 2
|
4.01 in
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 3
|
4.01 in
|
|
Cross sectional area of cylinder 1
|
12.63 in^2
|
|
Cross sectional area of cylinder 2
|
12.63 in^2
|
|
Cross sectional area of cylinder 3
|
12.63 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4490 psi
|
|
Maximum load on cylinder 1
|
54030 lb
|
|
Maximum load on cylinder 2
|
57570 lb
|
|
Maximum load on cylinder 3
|
58600 lb
|
|
Compressive strength of cylinder 1
|
4277.9 psi
|
|
Type of fracture pattern of cylinder 1
|
4
|
|
Compressive strength of cylinder 2
|
4558.2 psi
|
|
Compressive strength of cylinder 3
|
4639.7 psi
|
|
Type of fracture pattern of cylinder 2
|
4
|
|
Type of fracture pattern of cylinder 3
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
28 days
|
|
Age of specimen in hours
|
no data0 hours
|