The following testing has been tested in accordance with:
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Cured in accordance with ASTM C511
| Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
|---|---|---|---|---|---|
| 1 | 4.01 | 12.63 | 38831 | 3075.0 | 2 |
| 2 | 4.01 | 12.63 | 48984 | 3879.0 | 1 |
| 3 | 4.03 | 12.76 | 35657 | 2795 | 4 |
DIME Test ID: 2023-04-07-12-1
Number of specimens: 3
Compressive strength (to nearest 10 psi): 3250
Age of specimen: 7 days
Certified By: Spencer Adams
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Cured in accordance with ASTM C511
| Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
|---|---|---|---|---|---|
| 1 | 4.01 | 12.63 | 69009 | 5464.0 | 1 |
| 2 | 4.01 | 12.63 | 67865 | 5374.0 | 2 |
| 3 | 4.01 | 12.63 | 64026 | 5070 | 1 |
DIME Test ID: 2023-04-07-12-2
Number of specimens: 3
Compressive strength (to nearest 10 psi): 5300
Age of specimen: 28 days
Certified By: Spencer Adams
|