Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 212246 DEA: 053307A4 EFIS: 0514000027
QA Service Level: 1
DIST-CO-RTE-PM: 05-SLO-46-49.7/54.6
Work Description: Cholame Segment
Location Description:
Contractor Name: Atkinson Construction
Contractor Address: 18201 Von Karman - Suite 800, Irvine, CA 92612
Resident Engineer: Andrew Borrelli Structure Rep.: Dave Lewis
DIME Sample ID: 2023-04-03-10
TL Number from the TL Form:
Sample Submitted By Organization: CT D05 - Whitley Gardens Field Laboratory
Sample Organization Contact: 805-540-9933
Type of Sample: Quality Assurance
Type of Material: Soil
Sample Taken Date: 04/03/2023
Date that the sample was received by the laboratory/organization performing the testing: 04/03/2023
The quantity of what the sample constitutes: Sta 1225+00-1225+09 @ 24' wide
A brief description of the sample: Structure Backfill Geo Grid
From where was the sample collected: Job Site
Laboratory sample identification: 37074sbf2
Structure unique identifier:
Structure name: DS-21e
The fabricator/manufacturer/facility name: Sierra Pacific - Avenal
The fabricator's/manufacturer's product name for the sample:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Jobsite
Where the material sample would have been placed if not sampled:
DIME Test ID: 2023-04-03-10-1
Test Method: CTM 216-June 2011: Method of Test for Relative Compaction of Untreated and Treated Soils and Aggregates
Verified Date: 04/03/2023
Date Tested: 04/03/2023
Submitted By Organization: CT D05 - Whitley Gardens Field Laboratory
Organization Address: 102 South Whitley Gardens Drive,
Organization City: Paso Robles
Organization State: CA
Organization Zipcode: 93346
Organization Email: kyle.engen@dot.ca.gov
Organization Phone: (805) 540-9933
General Comments for this Test:
Test Result Compliance: does not comply
Additional Comments When Verified:
Is oversize material
|
Yes
|
In-place wet density
|
2.22
|
Percentage passing 3/4 in. sieve
|
89 %
|
Percentage retained on 3/4 in. sieve
|
11 %
|
Specific gravity of material passing 3/4 in. sieve
|
2.33
|
Specific gravity of material retained on 3/4 in. sieve
|
2.6 %
|
Coefficient for 3/4 in. aggregate
|
1.00
|
Corrected density
|
2.36
|
Relative compaction
|
94
|
% Moisture
|
no data
|
Optimum Moisture
|
no data
|