Project ID: 215425 DEA: 06360244 EFIS: 0613000005
QA Service Level: 1
DIST-CO-RTE-PM: 06-TUL-99-30.6/35.2
Work Description: Widen Freeway & Bridge Construction (Concrete Bridge)
Location Description:
Contractor Name: SECURITY PAVING COMPANY, INC.
Contractor Address: 13170 TELFAIR AVE, SYLMAR, CA, 91342
Resident Engineer: Javier Huerta Structure Rep.: Ramandeep Guraya
DIME Sample ID: 2023-01-26-51
TL Number from the TL Form:
Sample Submitted By Organization: CT D06 - Millbrook Field Laboratory
Sample Organization Contact: (559) 341-3953
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 01/26/2023
Date that the sample was received by the laboratory/organization performing the testing: 01/31/2023
The quantity of what the sample constitutes: 300 cy
A brief description of the sample: structural concrete
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier: 46-0279
Structure name:
The fabricator/manufacturer/facility name: Unknown
The concrete mix design number: 85Q41SIP
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 116523
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Chute discharge into wheel barrel
Where the material sample would have been placed if not sampled: Stem and Soffit J ST Bridge
From Lot No.:
Bag Lot No.:
DIME Test ID: 2023-01-26-51-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 02/02/2023
Date Tested: 01/31/2023
Submitted By Organization: CT D06 - Millbrook Field Laboratory
Organization Address: 1352 W. Olive Ave,
Organization City: Fresno
Organization State: CA
Organization Zipcode: 93728
Organization Email: tomas.silva@dot.ca.gov
Organization Phone: (559) 341-3953
General Comments for this Test: Required strength listed as 5000 PSI
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
1
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
4.01 in
|
|
Cross sectional area of cylinder 1
|
12.63 in^2
|
|
Compressive strength of cylinder (to nearest 10 psi)
|
4990 psi
|
|
Maximum load on cylinder 1
|
63000 lb
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Age of specimen
|
4 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2023-01-26-51-2
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 02/07/2023
Date Tested: 02/06/2023
Submitted By Organization: CT D06 - Millbrook Field Laboratory
Organization Address: 1352 W. Olive Ave,
Organization City: Fresno
Organization State: CA
Organization Zipcode: 93728
Organization Email: tomas.silva@dot.ca.gov
Organization Phone: (559) 341-3953
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Average diameter of cylinder 1
|
4.01 in
|
|
Average diameter of cylinder 2
|
4.01 in
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 3
|
4.01 in
|
|
Cross sectional area of cylinder 1
|
12.63 in^2
|
|
Cross sectional area of cylinder 2
|
12.63 in^2
|
|
Cross sectional area of cylinder 3
|
12.63 in^2
|
|
Compressive strength (to nearest 10 psi)
|
6480 psi
|
|
Maximum load on cylinder 1
|
85100 lb
|
|
Maximum load on cylinder 2
|
82230 lb
|
|
Maximum load on cylinder 3
|
78350 lb
|
|
Compressive strength of cylinder 1
|
6737.9 psi
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Compressive strength of cylinder 2
|
6510.7 psi
|
|
Compressive strength of cylinder 3
|
6203.5 psi
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Type of fracture pattern of cylinder 3
|
3
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
10 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2023-01-26-51-3
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 02/23/2023
Date Tested: 02/23/2023
Submitted By Organization: CT D06 - Millbrook Field Laboratory
Organization Address: 1352 W. Olive Ave,
Organization City: Fresno
Organization State: CA
Organization Zipcode: 93728
Organization Email: tomas.silva@dot.ca.gov
Organization Phone: (559) 341-3953
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Average diameter of cylinder 1
|
4.01 in
|
|
Average diameter of cylinder 2
|
4.01 in
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 3
|
4.01 in
|
|
Cross sectional area of cylinder 1
|
12.63 in^2
|
|
Cross sectional area of cylinder 2
|
12.63 in^2
|
|
Cross sectional area of cylinder 3
|
12.63 in^2
|
|
Compressive strength (to nearest 10 psi)
|
7630 psi
|
|
Maximum load on cylinder 1
|
95210 lb
|
|
Maximum load on cylinder 2
|
97840 lb
|
|
Maximum load on cylinder 3
|
95990 lb
|
|
Compressive strength of cylinder 1
|
7538.4 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
7746.6 psi
|
|
Compressive strength of cylinder 3
|
7600.2 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Type of fracture pattern of cylinder 3
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
27 days
|
|
Age of specimen in hours
|
no data0 hours
|