Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 214892 DEA: 06442554 EFIS: 0612000176 COOP: 061699
QA Service Level: 1
DIST-CO-RTE-PM: 06-KER-46-29.7/31.9
Work Description: CONVERT 2-LANE TO 4-LANE HMA PAVEMENT AND CONSTRUCT NEW BRIDGE.
Location Description: KERN COUNTY AT AND NEAR LOST HILLS FROM 0.2 MILE WEST OF CALIFORNIA AQUEDUCT BRIDGE TO 1.4 MILES EAST OF LOST HILLS ROAD
Contractor Name: GRANITE CONSTRUCTION COMPANY
Contractor Address: 3005 James Road, Bakersfield, CA 93308
Resident Engineer: Trever Shiplee Structure Rep.: Gabriel Macias
DIME Sample ID: 2023-01-13-30
TL Number from the TL Form:
Sample Submitted By Organization: CT D06 - Bakersfield Field Laboratory
Sample Organization Contact: 661-549-8281
Type of Sample: Department Acceptance
Type of Material: Concrete
Sample Taken Date: 01/13/2023
Date that the sample was received by the laboratory/organization performing the testing: 01/14/2023
The quantity of what the sample constitutes: 12 cylinder- 4X8
A brief description of the sample: Cylinder
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Lost Hills
The concrete mix design number: ND 20527
The truck number from where the sample was collected: back of truck
The batch plant ticket number from where the sample was collected: NOT PROVIDED
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Back of Truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2023-01-13-30-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 01/24/2023
Date Tested: 01/24/2023
Submitted By Organization: CT D06 - Bakersfield Field Laboratory
Organization Address: 1824 Norris Road,
Organization City: Bakersfield
Organization State: CA
Organization Zipcode: 93308
Organization Email: kulwinder.rai@dot.ca.gov
Organization Phone: (661) 549-8281
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C39 - Ground End
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4690 psi
|
|
Maximum load on cylinder 1
|
57770 lb
|
|
Maximum load on cylinder 2
|
59680 lb
|
|
Maximum load on cylinder 3
|
59530 lb
|
|
Compressive strength of cylinder 1
|
4595.9 psi
|
|
Type of fracture pattern of cylinder 1
|
4
|
|
Compressive strength of cylinder 2
|
4747.8 psi
|
|
Compressive strength of cylinder 3
|
4735.9 psi
|
|
Type of fracture pattern of cylinder 2
|
4
|
|
Type of fracture pattern of cylinder 3
|
4
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
10 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2023-01-13-30-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 02/10/2023
Date Tested: 02/10/2023
Submitted By Organization: CT D06 - Bakersfield Field Laboratory
Organization Address: 1824 Norris Road,
Organization City: Bakersfield
Organization State: CA
Organization Zipcode: 93308
Organization Email: kulwinder.rai@dot.ca.gov
Organization Phone: (661) 549-8281
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
6240 psi
|
|
Maximum load on cylinder 1
|
78570 lb
|
|
Maximum load on cylinder 2
|
76810 lb
|
|
Maximum load on cylinder 3
|
79970 lb
|
|
Compressive strength of cylinder 1
|
6250.6 psi
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Compressive strength of cylinder 2
|
6110.6 psi
|
|
Compressive strength of cylinder 3
|
6362 psi
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Type of fracture pattern of cylinder 3
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
28 days
|
|
Age of specimen in hours
|
no data0 hours
|