Project ID: 994068 DEA: 081C7204 EFIS: 0813000003
QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-15-R96.1/R124.3
Work Description: IMPORTED BORROW, SHOULDER BACKING, AND STRUCTURAL CONCRETE.
Location Description: SAN BERNARDINO ABOUT 22 MILES NORTHEAST OF BARSTOW AT VARIOUS LOCATIONS FROM 0.3 MILE SOUTH OF HARVARD ROAD OVERCROSSING TO 0.1 MILE NORTH OF RASOR ROAD OVERCROSSING
Contractor Name: SKANSKA USA CIVIL
Contractor Address: 1995 AGUA MANSA RD, RIVERSIDE, CA 92509
Resident Engineer: Thanh Pham Structure Rep.: Unknown
DIME Sample ID: 2023-01-11-23
TL Number from the TL Form: 11
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 01/11/2023
Date that the sample was received by the laboratory/organization performing the testing: 01/12/2023
The quantity of what the sample constitutes: 4
A brief description of the sample: 6x12
From where was the sample collected: Job Site
Laboratory sample identification: 1047-11
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: mitsu
The concrete mix design number: sc590b38
The truck number from where the sample was collected: 2207
The batch plant ticket number from where the sample was collected: 6737198
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2023-01-11-23-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap Cured in accordance with ASTM C511
Verified Date: 02/09/2023
Date Tested: 02/08/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
|
Cross sectional area of cylinder 2
|
28.18 in^2
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Compressive strength (to nearest 10 psi)
|
5140 psi
|
|
Average diameter of cylinder 1
|
6.00 in
|
|
Average diameter of cylinder 2
|
5.99 in
|
|
Compressive strength of cylinder 1
|
5250.1 psi
|
|
Compressive strength of cylinder 2
|
5022.7 psi
|
|
Maximum load on cylinder 1
|
148420 lb
|
|
Maximum load on cylinder 2
|
141540 lb
|
|
Type of fracture pattern of cylinder 1
|
1
|
|
Type of fracture pattern of cylinder 2
|
1
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Age of specimen
|
28 days
|