Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 993253 DEA: 033F0604 EFIS: 0312000052
QA Service Level: 1
DIST-CO-RTE-PM: 03-GLE-162-76.3/78.6
Work Description:
Location Description:
Contractor Name: GOLDEN STATE BRIDGE
Contractor Address: 3701 Mallard Drive, Benicia, CA 94510
Resident Engineer: Dustin Watts Structure Rep.: Matt Crete
DIME Sample ID: 2022-12-20-3
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Sacramento Field Office
Sample Organization Contact: (916) 2058871
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Headed Bars
Sample Taken Date: 12/20/2022
Date that the sample was received by the laboratory/organization performing the testing: 12/21/2022
The quantity of what the sample constitutes: Group of 712 heads / 356 bars
A brief description of the sample: Headed #8 bars
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: CMC Rebar Fresno, CA
Production or Authorization Testing: Production Testing
Rebar Heat Number(s): 4123208
Head Manufacturer Lot Number(s): 10
Rebar Size: #8
Headed Bar Model Name: HRC 555
Size of Head: Reduced Size - 4x
Head Connection Type: Forged
Head Shape: Circular
Rebar Manufacturer: CMC Steel Arizona
Head Manufacturer: NA
Head Fabricator: CMC Rebar Fresno
Material Standard Code: ASTM A706
Headed Bar Unique ID: 4FG-17-01
DIME Test ID: 2022-12-20-3-1
Test Method: ASTM A970-18: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 12/29/2022
Date Tested: 12/28/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 10 | 0.79 | 76166 | 96413 | Ok Necking | spaine |
| |
Temperature
|
72 f
|
UTM
|
400kip
|
DIME Test ID: 2022-12-20-3-2
Test Method: ASTM A970-18: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 12/29/2022
Date Tested: 12/28/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 10 | 0.79 | 79464 | 100587 | Ok Necking | spaine |
| |
Temperature
|
72 f
|
UTM
|
400kip
|
DIME Test ID: 2022-12-20-3-3
Test Method: ASTM A970-18: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 12/29/2022
Date Tested: 12/28/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples
|
1
|
Lot # | Area (sqin) | Peak Load (lbf) | Tensile Strength (psi) | Comments | Tested By | 10 | 0.79 | 79219 | 100277 | Ok Necking | spaine |
| |
Temperature
|
72 f
|
UTM
|
400kip
|