Print Report | Back to Sample Detail

Sample Record for 2022-12-08-6

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 214993 DEA: 051F5004 EFIS: 0514000003 QA Service Level: 1
DIST-CO-RTE-PM: 05-SB-101,135-70.6/71.2;0.1
Work Description: CONSTRUCT CONCRETE BRIDGE, BRIDGE REMOVAL, COLD PLANE, PLACE HMA.
Location Description: SANTA BARBARA COUNTY AT LOS ALAMOS ON ROUTE 101 FROM 0.3 MILE SOUTH TO 0.3 MILE NORTH OF ROUTE 101/135 SEPARATION AND ON ROUTE 135 AT ROUTE 101/135 SEPARATION
Contractor Name: CAL PORTLAND CONSTRUCTION
Contractor Address: 1625 E Donovan Road, Santa Maria, CA 93454
Resident Engineer: Jason Torres Structure Rep.: Alex Martinez

Sample Information

DIME Sample ID: 2022-12-08-6
TL Number from the TL Form:
Sample Submitted By Organization: CT D05 - Santa Maria Field Laboratory
Sample Organization Contact: 8053191237
Type of Sample: Department Acceptance
Type of Material: Concrete
Sample Taken Date: 12/08/2022
Date that the sample was received by the laboratory/organization performing the testing: 12/09/2022
The quantity of what the sample constitutes: 300 cu yds
A brief description of the sample: Bridge Deck Concrete
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Calportland/Donaven

Material Information

The concrete mix design number: 675RHS1260
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: NA
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Discharge from concrete truck into wheelbarrow
Where the material sample would have been placed if not sampled: bridge deck
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 5

DIME Test ID: 2022-12-08-6-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 12/15/2022
Date Tested: 12/15/2022
Submitted By Organization: CT D05 - Santa Maria Field Laboratory
Organization Address: 2053 Preisker Lane, Suite E,
Organization City: Santa Maria
Organization State: CA
Organization Zipcode: 93427
Organization Email: isaac.gleffe@dot.ca.gov
Organization Phone: (805) 319-1237
General Comments for this Test: deck pour: 7-day bk
Test Result Compliance: not applicable
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 3.98 in
Cross sectional area of cylinder 1 12.54 in^2
Cross sectional area of cylinder 2 12.55 in^2
Cross sectional area of cylinder 3 12.45 in^2
Compressive strength (to nearest 10 psi) 3670 psi
Maximum load on cylinder 1 44476 lb
Maximum load on cylinder 2 45902 lb
Maximum load on cylinder 3 47125 lb
Type of fracture pattern of cylinder 1 4
Type of fracture pattern of cylinder 2 4
Type of fracture pattern of cylinder 3 4
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 no data0
Correction factor for cylinder 2 no data0
Correction factor for cylinder 3 no data0
Age of specimen 7 days
Age of specimen in hours 168 hours

Test 2 of 5

DIME Test ID: 2022-12-08-6-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 01/10/2023
Date Tested: 01/05/2023
Submitted By Organization: CT D05 - Santa Maria Field Laboratory
Organization Address: 2053 Preisker Lane, Suite E,
Organization City: Santa Maria
Organization State: CA
Organization Zipcode: 93427
Organization Email: isaac.gleffe@dot.ca.gov
Organization Phone: (805) 319-1237
General Comments for this Test: deck pour: 28-day bk.
Test Result Compliance: not applicable
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 3.98 in
Average diameter of cylinder 2 3.98 in
Average diameter of cylinder 3 3.97 in
Cross sectional area of cylinder 1 12.45 in^2
Cross sectional area of cylinder 2 12.48 in^2
Cross sectional area of cylinder 3 12.41 in^2
Compressive strength (to nearest 10 psi) 5270 psi
Maximum load on cylinder 1 68303 lb
Maximum load on cylinder 2 64396 lb
Maximum load on cylinder 3 63916 lb
Type of fracture pattern of cylinder 1 4
Type of fracture pattern of cylinder 2 4
Type of fracture pattern of cylinder 3 4
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 28 days
Age of specimen in hours 1120 hours

Test 3 of 5

DIME Test ID: 2022-12-08-6-3
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 02/23/2023
Date Tested: 01/19/2023
Submitted By Organization: CT D05 - Santa Maria Field Laboratory
Organization Address: 2053 Preisker Lane, Suite E,
Organization City: Santa Maria
Organization State: CA
Organization Zipcode: 93427
Organization Email: isaac.gleffe@dot.ca.gov
Organization Phone: (805) 319-1237
General Comments for this Test: deck pour: 42-day bk.
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 3.99 in
Average diameter of cylinder 2 3.98 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.51 in^2
Cross sectional area of cylinder 2 12.48 in^2
Cross sectional area of cylinder 3 12.59 in^2
Compressive strength (to nearest 10 psi) 5860 psi
Maximum load on cylinder 1 74611 lb
Maximum load on cylinder 2 75348 lb
Maximum load on cylinder 3 70453 lb
Type of fracture pattern of cylinder 1 4
Type of fracture pattern of cylinder 2 4
Type of fracture pattern of cylinder 3 4
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 42 days
Age of specimen in hours 1008 hours

Test 4 of 5

DIME Test ID: 2022-12-08-6-4
Test Method: CTM 556-January 2018: Method of Test for Slump of Fresh Portland Cement Concrete
Verified Date: 12/08/2022
Date Tested: 12/08/2022
Submitted By Organization: CT D05 - Santa Maria Field Laboratory
Organization Address: 2053 Preisker Lane, Suite E,
Organization City: Santa Maria
Organization State: CA
Organization Zipcode: 93427
Organization Email: isaac.gleffe@dot.ca.gov
Organization Phone: (805) 319-1237
General Comments for this Test: slump
Test Result Compliance: does not comply
Additional Comments When Verified:
Slump 5.25 inch

Test 5 of 5

DIME Test ID: 2022-12-08-6-5
Test Method: CTM 557-June 2020: Method of Test for Temperature of Freshly Mixed Hydraulic Cement Concrete
Verified Date: 12/08/2022
Date Tested: 12/08/2022
Submitted By Organization: CT D05 - Santa Maria Field Laboratory
Organization Address: 2053 Preisker Lane, Suite E,
Organization City: Santa Maria
Organization State: CA
Organization Zipcode: 93427
Organization Email: isaac.gleffe@dot.ca.gov
Organization Phone: (805) 319-1237
General Comments for this Test: Temp.
Test Result Compliance: complies
Additional Comments When Verified:
Temperature 64 F