REPORT OF LABORATORY TESTING |
||||
Resident Engineer: |
Mary Bokova |
Date Reported: |
08/12/2015 |
|
Address: |
TL Number: |
202502 |
||
City: |
||||
Project Name: INCREASE ON AND OFF-RAMP RADIUS AND LANE WIDTH OF ILLINOISTOWN OC. |
||||
Prime Contractor: Independent Structures Inc. |
||||
Sample Taken Date: |
07/22/2015 |
Mix Design: |
Unknown |
|
Contractor: Unknown |
Location : PLACER COUNTY NEAR COLFAX AT ILLINOISTOWN OVERCROSSING |
|||
Structure unique identifier: Unknown |
||||
Structure name: Unknown |
||||
Location of Pour: Unknown |
The following testing has been tested in accordance with:
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Cured in accordance with ASTM C511
Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 6.03 | 28.56 | 84482 | 2958.1 | 1 |
2 | 6.04 | 28.65 | 81662 | 2850.3 | 1 |
DIME Test ID: 2015-07-22-2-1
Number of specimens: 2
Compressive strength (to nearest 10 psi): 2900
Age of specimen: 21 days
Certified By: Bang Nguyen
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Cured in accordance with ASTM C511
Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 6.02 | 28.46 | 76228 | 2678.4 | 1 |
2 | 6.02 | 28.46 | 80535 | 2829.8 | 1 |
DIME Test ID: 2015-07-22-2-2
Number of specimens: 2
Compressive strength (to nearest 10 psi): 2750
Age of specimen: 14 days
Certified By: Bang Nguyen
*Subject to final inspection by the Resident Engineer. |
TL- Report of Laboratory Testing