Contract # 033H4504 Cty ED Rte 50 PM 33.8/34.2

Vendor #


REPORT OF LABORATORY TESTING

Resident Engineer:

Jody Phillips

Date Reported:

01/10/2023

Address:

TL Number:

206115

City:

Project Name: CONSTRUCT RW, WIDEN RDWY, COLD PLANE AC PVMT, & HMA OVERLAY.

Prime Contractor: BRIDGEWAY CIVIL CONSTRUCTORS, INC.

Sample Taken Date:

11/15/2022

Mix Design:

CT072CR5WA

Contractor: Unknown

Location : EL DORADO COUNTY AT FRESH POND FROM 0.6 TO 0.2 MILE WEST OF FOREST ROAD/OUTER LIMITS LANE

Structure unique identifier:

Structure name:

Location of Pour:


The following testing has been tested in accordance with:

ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens

Capped in accordance with ASTM C617/CTM521

Cured in accordance with ASTM C511

SpecimenAverage diameter of cylinder (in)Cross sectional area of cylinder (in^2)Maximum load on cylinder (lb)Compressive strength of cylinder (psi)Type of fracture pattern of cylinder
14.0112.63434783443.04
24.0312.76451113537.04
34.0012.573923131222

DIME Test ID: 2022-11-15-33-1
Number of specimens: 3
Compressive strength (to nearest 10 psi): 3370
Age of specimen: 28 days
Certified By: Spencer Adams


ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens

Capped in accordance with ASTM C617/CTM521

Cured in accordance with ASTM C511

SpecimenAverage diameter of cylinder (in)Cross sectional area of cylinder (in^2)Maximum load on cylinder (lb)Compressive strength of cylinder (psi)Type of fracture pattern of cylinder
14.0112.63537144253.01
24.0112.63468843712.01
34.0112.635192941121

DIME Test ID: 2022-11-15-33-2
Number of specimens: 3
Compressive strength (to nearest 10 psi): 4030
Age of specimen: 28 days
Certified By: Spencer Adams



Summary of Items Observed and Conversations:

Comments: This report is for the purpose of reporting test results.
Should you require recommendations concerning repairs or remedial efforts please contact the METS representative,
who represents the Materials Engineering and Testing Services for your project.

*Subject to final inspection by the Resident Engineer.