Print Report | Back to Sample Detail

Sample Record for 2022-09-14-58

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 993340 DEA: 051J7504 EFIS: 0518000039 MINOR: 05A2318 QA Service Level: 1
DIST-CO-RTE-PM: 05-SB-101-90
Work Description: Install CMS Sign Structure US 101 NB 0.3 Miles N of Donovan Rd
Location Description: In Santa Maria
Contractor Name: Pelagic Engineering
Contractor Address: 3600 Harbor Blvd #85, Oxnard, CA 93035
Resident Engineer: Thomas Petersen Structure Rep.: Alex Martinez

Sample Information

DIME Sample ID: 2022-09-14-58
TL Number from the TL Form:
Sample Submitted By Organization: CT D05 - Santa Maria Field Laboratory
Sample Organization Contact: 8053191237
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 09/14/2022
Date that the sample was received by the laboratory/organization performing the testing: 09/15/2022
The quantity of what the sample constitutes: 19.10 CY
A brief description of the sample: 72GA1NOP
From where was the sample collected: Job Site
Laboratory sample identification: 220914B
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Martin Mariatta SLO

Material Information

The concrete mix design number: 72GA1NOP
The truck number from where the sample was collected: load 1
The batch plant ticket number from where the sample was collected: NA
Concrete batch plant: Martin Marietta SLO
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Discharge from concrete truck into wheelbarrow.
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 5

DIME Test ID: 2022-09-14-58-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 09/22/2022
Date Tested: 09/21/2022
Submitted By Organization: CT D05 - Santa Maria Field Laboratory
Organization Address: 2053 Preisker Lane, Suite E,
Organization City: Santa Maria
Organization State: CA
Organization Zipcode: 93427
Organization Email: isaac.gleffe@dot.ca.gov
Organization Phone: (805) 319-1237
General Comments for this Test: avg.3, 7 day BK. Complies
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 4.02 in
Average diameter of cylinder 2 4.01 in
Average diameter of cylinder 3 4.01 in
Cross sectional area of cylinder 1 12.69 in^2
Cross sectional area of cylinder 2 12.63 in^2
Cross sectional area of cylinder 3 12.63 in^2
Compressive strength (to nearest 10 psi) 4080 psi
Maximum load on cylinder 1 51976 lb
Maximum load on cylinder 2 53310 lb
Maximum load on cylinder 3 49442 lb
Type of fracture pattern of cylinder 1 4
Type of fracture pattern of cylinder 2 3
Type of fracture pattern of cylinder 3 4
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 7 days
Age of specimen in hours no data0 hours

Test 2 of 5

DIME Test ID: 2022-09-14-58-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 10/12/2022
Date Tested: 10/12/2022
Submitted By Organization: CT D05 - Santa Maria Field Laboratory
Organization Address: 2053 Preisker Lane, Suite E,
Organization City: Santa Maria
Organization State: CA
Organization Zipcode: 93427
Organization Email: isaac.gleffe@dot.ca.gov
Organization Phone: (805) 319-1237
General Comments for this Test: AVG. 3, 28 day BK , Complies
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 4.02 in
Average diameter of cylinder 2 4.01 in
Average diameter of cylinder 3 4.01 in
Cross sectional area of cylinder 1 12.69 in^2
Cross sectional area of cylinder 2 12.6 in^2
Cross sectional area of cylinder 3 12.62 in^2
Compressive strength (to nearest 10 psi) 6410 psi
Maximum load on cylinder 1 79826 lb
Maximum load on cylinder 2 81749 lb
Maximum load on cylinder 3 81357 lb
Type of fracture pattern of cylinder 1 4
Type of fracture pattern of cylinder 2 4
Type of fracture pattern of cylinder 3 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 28 days
Age of specimen in hours 672 hours

Test 3 of 5

DIME Test ID: 2022-09-14-58-3
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/01/2022
Date Tested: 10/26/2022
Submitted By Organization: CT D05 - Santa Maria Field Laboratory
Organization Address: 2053 Preisker Lane, Suite E,
Organization City: Santa Maria
Organization State: CA
Organization Zipcode: 93427
Organization Email: isaac.gleffe@dot.ca.gov
Organization Phone: (805) 319-1237
General Comments for this Test: avg.3 42 day BK
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 1
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 4.01 in
Compressive strength of cylinder (to nearest 10 psi) 5960 psi
Maximum load on cylinder 1 75576 lb
Type of fracture pattern of cylinder 1 5
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 no data0
Age of specimen 42 days
Age of specimen in hours 1008 hours

Test 4 of 5

DIME Test ID: 2022-09-14-58-4
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 09/22/2022
Date Tested: 09/14/2022
Submitted By Organization: CT D05 - Santa Maria Field Laboratory
Organization Address: 2053 Preisker Lane, Suite E,
Organization City: Santa Maria
Organization State: CA
Organization Zipcode: 93427
Organization Email: isaac.gleffe@dot.ca.gov
Organization Phone: (805) 319-1237
General Comments for this Test: complies
Test Result Compliance: complies
Additional Comments When Verified:
Temperature 71 F

Test 5 of 5

DIME Test ID: 2022-09-14-58-5
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 09/22/2022
Date Tested: 09/14/2022
Submitted By Organization: CT D05 - Santa Maria Field Laboratory
Organization Address: 2053 Preisker Lane, Suite E,
Organization City: Santa Maria
Organization State: CA
Organization Zipcode: 93427
Organization Email: isaac.gleffe@dot.ca.gov
Organization Phone: (805) 319-1237
General Comments for this Test: does not comply
Test Result Compliance: does not comply
Additional Comments When Verified:
Slump 6.25 inch