Sample Record for 2022-08-18-47

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 215677 DEA: 044G0804 EFIS: 0412000332 COOP: 042676 QA Service Level: 1
DIST-CO-RTE-PM: 04-SOL-80-R10.4/30.2
Work Description: Highway widening, overhead signs, and electronic toll system.
Location Description: In Solano County in Fairfield and Vacaville from 1.0 mile west of Red Top Road Undercrossing to 0.4 mile east of Leisure Town Road Overcrossing.
Contractor Name: O.C. JONES & SONS, INC.
Contractor Address: 1520 Fourth Street, Berkeley, CA 94710
Resident Engineer: Justen Tatum Structure Rep.: Kelsey Littell

Sample Information

DIME Sample ID: 2022-08-18-47
TL Number from the TL Form:
Sample Submitted By Organization: Con-Fab California Corporation - Shafter
Sample Organization Contact: (661) 630-7162
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 08/18/2022
Date that the sample was received by the laboratory/organization performing the testing: 08/19/2022
The quantity of what the sample constitutes: One Girder
A brief description of the sample: PCC 4''X8'' Test Cylinder
From where was the sample collected: Manufacturer
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Con-Fab California, LLC

Material Information

The concrete mix design number: SCCS9015F
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 2678
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Casting Bed Alpha East
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 7

DIME Test ID: 2022-08-18-47-1
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 09/07/2022
Date Tested: 08/18/2022
Submitted By Organization: Con-Fab California Corporation - Shafter
Organization Address: 701 Golds Avenue,
Organization City: Shafter
Organization State: CA
Organization Zipcode: 93263
Organization Email: benjamina@confabca.com
Organization Phone: (661) 630-3283
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Temperature 79 F

Test 2 of 7

DIME Test ID: 2022-08-18-47-2
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 09/07/2022
Date Tested: 08/18/2022
Submitted By Organization: Con-Fab California Corporation - Shafter
Organization Address: 701 Golds Avenue,
Organization City: Shafter
Organization State: CA
Organization Zipcode: 93263
Organization Email: benjamina@confabca.com
Organization Phone: (661) 630-3283
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Slump 28 inch

Test 3 of 7

DIME Test ID: 2022-08-18-47-3
Test Method: ASTM C138-17a: Standard Test Method for Density (Unit Weight), Yield, and Air Content (Gravimetric) of Concrete
Verified Date: 09/07/2022
Date Tested: 08/18/2022
Submitted By Organization: Con-Fab California Corporation - Shafter
Organization Address: 701 Golds Avenue,
Organization City: Shafter
Organization State: CA
Organization Zipcode: 93263
Organization Email: benjamina@confabca.com
Organization Phone: (661) 630-3283
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Identification of concrete represented by the sample Girder
Volume of the measure 0.25 ft^3
Density of concrete 150.1 lb/ft^3
Yield of concrete no data
Relative yield of the batch no data
Cement content no data
Air content no data

Test 4 of 7

DIME Test ID: 2022-08-18-47-4
Test Method: ASTM C231-17a: Standard Test Method for Air Content of Freshly Mixed Concrete by the Pressure Method
Verified Date: 09/07/2022
Date Tested: 08/18/2022
Submitted By Organization: Con-Fab California Corporation - Shafter
Organization Address: 701 Golds Avenue,
Organization City: Shafter
Organization State: CA
Organization Zipcode: 93263
Organization Email: benjamina@confabca.com
Organization Phone: (661) 630-3283
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Air content 1.4 %

Test 5 of 7

DIME Test ID: 2022-08-18-47-5
Test Method: CTM TEMP1-16: Test Method for Monitoring Precast Concrete Curing Temperature (Curing temperature)
Verified Date: 09/07/2022
Date Tested: 08/18/2022
Submitted By Organization: Con-Fab California Corporation - Shafter
Organization Address: 701 Golds Avenue,
Organization City: Shafter
Organization State: CA
Organization Zipcode: 93263
Organization Email: benjamina@confabca.com
Organization Phone: (661) 630-3283
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Precast Maximum Curing Temperature 145.5 °F

Test 6 of 7

DIME Test ID: 2022-08-18-47-6
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 09/07/2022
Date Tested: 08/19/2022
Submitted By Organization: Con-Fab California Corporation - Shafter
Organization Address: 701 Golds Avenue,
Organization City: Shafter
Organization State: CA
Organization Zipcode: 93263
Organization Email: benjamina@confabca.com
Organization Phone: (661) 630-3283
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? no data
Apparent mass of submerged cylinder 1 8.9 lb
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Compressive strength (to nearest 10 psi) 5100 psi
Maximum load on cylinder 1 65910 lb
Maximum load on cylinder 2 62155 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 5
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen no data0 days
Age of specimen in hours 18 hours
Serial number of delivery ticket, if available no data

Test 7 of 7

DIME Test ID: 2022-08-18-47-7
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 09/07/2022
Date Tested: 08/25/2022
Submitted By Organization: Con-Fab California Corporation - Shafter
Organization Address: 701 Golds Avenue,
Organization City: Shafter
Organization State: CA
Organization Zipcode: 93263
Organization Email: benjamina@confabca.com
Organization Phone: (661) 630-3283
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? no data
Apparent mass of submerged cylinder 1 8.9 lb
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 6580 psi
Maximum load on cylinder 1 83560 lb
Maximum load on cylinder 2 82445 lb
Maximum load on cylinder 3 78230 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 5
Type of fracture pattern of cylinder 3 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 7 days
Age of specimen in hours no data0 hours
Serial number of delivery ticket, if available no data